| Installation & User Manual |
June 2013 | Ed 19UK |
|
|
Installation
Prior to installation please check that:
•the serial numbers on the transducer, amplifier and lid of amplifier box agree. The serial numbers are to be found on the inside of the lid of the amplifier box on the bottom line - amplifier S/N and transducer S/N on the range label.
•the transducer is fitted in the correct tank.
•the transducer is correctly connected to the amplifier.
NOTE: The white and brown wires in the transducer cable are only used when a Pt100 sensor is built into the transducer.
•all cable glands are properly secured to the amplifier box. Use torque of 6 Nm.
•the amplifier box is mounted in such a way that the breather tube cannot be flooded.
•the cable is fastened with cable clips with a distance of max. 50 cm.
•the cable isolation is not damaged (cracks, weld spatter, burns etc.).
•
As for flange mounted applications it is recommended that a ball valve is fitted in the front of the transducer to facilitate testing and calibrating of the transmitter.
Using a shielded cable to the