Emerson MAS 2600 user manual Absolute Transducers, Basic Rules, Forepeak Tank

Page 8

Installation & User Manual

Ed 19UK

June 2013

 

 

Absolute Transducers:

The Absolute Transmitter is typically used if the amplifier is exposed to water, e.g. on open deck. The Absolute Transmitter is available in 2 ranges: 0-20 and 0-35 mH2O. In practice this means 10 mH2O less than the nominal range because of the atmospheric pressure which must be taken into consideration when choosing the transducer.

A transducer with an effective range larger than the tank height should be selected.

Basic Rules:

1.The selected measuring range must be larger than the tank height.

2.The selected measuring range must be larger than tank height + vent pipe height

2

EXAMPLE: Tank height

=

6 m

Vent pipe height =

14 m

1. The selected measuring range must be larger than 6 m due to the height of the tank.

2. The selected measuring range must be larger than

6 + 14

= 10 m due to the total height of the

2

 

 

tank and the vent pipe combined.

Select a transducer with a measuring range of 16 mH2O as this is the next measuring range larger than 10 m.

Turn the range select switch on the amplifier to range No. 7.

Normally the selection of transducer, range select and calibration are done by DAMCOS.

Special consideration applies to e.g. forepeak tanks and draft measuring when selecting the measuring range of the transducer.

Forepeak Tank:

Transducer measuring range > tank height: Select the next measuring range.

EXAMPLE: Tank height 12 m.

Based on the tank height a transducer with a measuring range of 16 mH2O should be selected.

However, due to the dynamic conditions in the forepeak tank, a transducer with a measuring range of 35 mH2O, i.e. the next in line, should be selected.

Turn amplifier range select switch to range No. 6.

Page 8 of 28

Image 8
Contents MAS2600 Table of contents Application MAS2600 Tank Contents TransmitterDescription and Operation Technical Specifications MAS2600 Ordering Information Transducer RangesType Gauge TransmitterGauge and High Temperature Gauge Transducers Selecting the Measuring RangeSelecting the Transducer Type Transducer type 3.5 bar abs 2.0 bar absForepeak Tank Absolute TransducersBasic Rules Temperature Sensor MAS2600-XXX-XX-X/XX DraftBrackets for Internal Mounting drawing no. G022P010 Pole Mounting drawing no. G022P011Pipe End Mounting drawing no. G022P015 Flange Mounting drawing no. G022P013Flexible rubber tube mounting 80 ºC drawing no. G022P001 DN25 flange with 1 ball valve drawing no. G022P019 75.0 Deck Box 165B9035 Handling Installation June Intrinsically Safe Installation XXXXXX-YYYYEd 19UK Any 28V / 300R Testing and Recalibrating Testing= 12 mA Trd .range − + PCalculated output at atmospheric pressure Trouble Shooting Maintenance and Trouble ShootingMaintenance MAS2600 Test sheet FAXEmerson Process Management