Emerson MAS 2600 user manual Technical Specifications

Page 4

Installation & User Manual

Ed 19UK

Technical Specifications

Transducer Ranges:

Gauge: 0-3.5 / 0-7 / 0-16 / 0-35 m H2O.

Absolute:

0-20.394 / 0-35.690 m H2O.

Programmable Measuring Ranges:

Each transducer range is programmable in 8 steps.

Accuracy:

±0.25% F.S. at 20°C.

Stability:

Max. ± 0.1% / Year.

TEB (Total Error Band):

± 2.0% F.S. at -20 to +80°C.

EMC immunity influence < ±0.5%FS

Overload Capability:

Min. 4 x transducer range with no changes in calibration.

6 x transducer range burst pressure.

Built-in Temperature Sensor Pt100:

Optional.

Power Supply:

The Power Supply can vary from 17-33 VDC. Permissible load resistance is shown graphically below. Calculation formula:

ULoop -17V

Rloop max. (Kohm) = 25mA

Max. load resistance at various power supply

(ohm)

700

 

 

 

 

 

600

 

 

 

 

 

500

 

 

 

 

 

resistance

400

 

 

 

 

 

300

 

 

 

 

 

200

 

 

 

 

 

100

 

 

 

 

 

0

 

 

 

 

 

17

20

23

26

29

32

Load

 

Power supply (V)

 

 

 

 

Page 4 of 28

June 2013

Output Current:

4-20 mA DC, loop powered 2-wire system.

Current Limiting:

Max:

25 mA

Sensor Materials:

Housing: Titanium Grade 2

Diaphragm: Titanium Grade 4

Operating Temperature Ranges:

 

Transducer:

-20 to +125°C

Standard cable:

-20 to +

80°C

High temperature cable:

-20 to +125°C

Amplifier:

-40 to +

85°C

Protection Class:

 

Transducer:

IP 68

Amplifier:

IP 56

Intrinsic Safety:

Ex ia IIC T4 compliant.

Max. 75 m cable between transducer and transmitter amplifier.

Transmitter dimensions

Amplifier box:

 

110.0

55.0

 

98.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2600 SERIES

 

 

 

 

4-20 mA TWO WIRE TRANSMITTER

75.0

4 pcs. ø4.5

45.0

x EEX ia

C T5

S/N: 2600

 

CERTIFICATE REF.: 90-C.95948 Tamb.: -40 to +85 °C

 

Lint = 20 uH

Cint = 10 nF

Umax = 33 V

IK=< 45 mA

 

 

 

 

 

MARINE AUTOMATION DENMARK

 

 

 

 

 

 

 

 

 

PG11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/8" NPT

cable gland

 

Use 4x20mm bolts and nuts

 

 

 

 

 

for suspension on a 4mm

 

 

vent fitting

 

thick surface

Transducer:

3.06-core vented cable, ø8.0

 

 

 

 

 

 

30.0

 

 

 

25.0

 

 

 

 

 

 

 

 

 

 

 

 

 

120.0

Front view

 

Image 4
Contents MAS2600 Table of contents Description and Operation MAS2600 Tank Contents TransmitterApplication Technical Specifications MAS2600 Ordering Information Transducer RangesType Gauge TransmitterGauge and High Temperature Gauge Transducers Selecting the Measuring RangeSelecting the Transducer Type Transducer type 3.5 bar abs 2.0 bar absBasic Rules Absolute TransducersForepeak Tank Temperature Sensor MAS2600-XXX-XX-X/XX DraftBrackets for Internal Mounting drawing no. G022P010 Pole Mounting drawing no. G022P011Pipe End Mounting drawing no. G022P015 Flange Mounting drawing no. G022P013Flexible rubber tube mounting 80 ºC drawing no. G022P001 DN25 flange with 1 ball valve drawing no. G022P019 75.0 Deck Box 165B9035 Handling Installation June Intrinsically Safe Installation XXXXXX-YYYYEd 19UK Any 28V / 300R Testing and Recalibrating Testing= 12 mA Trd .range − + PCalculated output at atmospheric pressure Maintenance Maintenance and Trouble ShootingTrouble Shooting MAS2600 Test sheet FAXEmerson Process Management