Installing Potential Transformers for Three-Phase Service Greater

Than 277V

Potential transformers are required when metering services greater than the rated voltage input of the meter. Potential transformers are used to reduce the line-to-neutral voltage of the service to 120V. The accuracy class should be 0.3% or better, with a burden rating of 30VA.

For applications in Canada, Measurement Canada approved potential transformers are required. Measurement Canada requires an accuracy class of 0.3% or better, with a 150VA rating.

NOTE: Potential transformer burden depends on the control voltage source. If control voltage is provided separately (not derived from the metered voltage), then lower transformer burden may be acceptable. Contact your local Schneider Electric representative for details.

Mount the potential transformer enclosure between the supply voltage and the PowerLogic meters as shown in Figure 4. Transformer configuration must be YY (wye-wye).

In Figure 4, the meter is powered from the potential transformers that are fed from a breaker within the 600Y/347V panel. The CT cable is connected to the shorting enclosure before connecting to the CTs in the panel.

©2013 Schneider Electric All Rights Reserved

9

Image 17
Contents PowerLogicTM Series EM4000 Page Please note Important InformationFCC Part 68 Notice FCC Part 15 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved System Description PowerLogic EM4000 series System SpecificationsIntroduction PowerLogic EM4000 series meter specifications Front Panel Display PowerLogic EM4080 front panelPowerLogic EM4033 and PowerLogic EM4080 internal view Electrical Standards Compliance Safety PrecautionsPre-Installation InstallationPre-Installation Checklist ReceivingMounting the PowerLogic EM4000 meter Installation ProceduresAccess to Power and Lighting 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved PowerLogic EM4000 meter three-phase Delta service connection Delta service meteringInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Shows a 5A CT connected to the converter StepsPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Modbus RTU Communications Connecting the CommunicationsConnecting the Ethernet Cable Start-Up Sequence Connecting Pulse InputsManually Testing Communications Display Navigation Normal ModeDiagnostics Mode Recording the Meter Map Installation Record sample shown Fuse Replacement MaintenanceRegulatory Compliance Equipment servicing and accessGraphical symbols that appear on equipment Numerics IndexPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric