PowerLogicTM Series EM4000 | |
11/2013 | Installation Guide |
|
|
Installing Potential Transformers for
Than 277V
Potential transformers are required when metering services greater than the rated voltage input of the meter. Potential transformers are used to reduce the
For applications in Canada, Measurement Canada approved potential transformers are required. Measurement Canada requires an accuracy class of 0.3% or better, with a 150VA rating.
NOTE: Potential transformer burden depends on the control voltage source. If control voltage is provided separately (not derived from the metered voltage), then lower transformer burden may be acceptable. Contact your local Schneider Electric representative for details.
Mount the potential transformer enclosure between the supply voltage and the PowerLogic meters as shown in Figure 4. Transformer configuration must be YY
In Figure 4, the meter is powered from the potential transformers that are fed from a breaker within the 600Y/347V panel. The CT cable is connected to the shorting enclosure before connecting to the CTs in the panel.
©2013 Schneider Electric All Rights Reserved | 9 |