Schneider Electric manual PowerLogic EM4000 series meter specifications

Page 10

PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

Table 1: PowerLogic EM4000 series meter specifications

Specification

PowerLogic EM4033 meter

PowerLogic EM4080 meter

 

 

 

Dimensions

Height: 13.125 in. (33.5 cm)

Height: 13.125 in. (33.5 cm)

 

Width: 12 in. (30.5 cm)

Width: 12 in. (30.5 cm)

 

Depth: 2.125 in. (5.5 cm)

Depth: 2.125 in. (5.5 cm)

 

 

 

Weight

8.77 lb (3.98 kg)

8.77 lb (3.98 kg)

 

 

 

Sense voltage

100V to 300V 50/60Hz

100V to 300V 50/60Hz

 

2W+N+Protective Earth Wye

2W+N+Protective Earth Wye

 

3W+N+Protective Earth Wye

3W+N+Protective Earth Wye

 

3W+Protective Earth Delta

3W+Protective Earth Delta

 

 

 

Control voltage and current

North America:

North America:

 

• 120V 125 mA 60 Hz

• 120V 125 mA 60 Hz

 

• 277V 54 mA 60 Hz

• 277V 54 mA 60 Hz

 

 

 

Current transformers

0.333 V secondary CT

80 mA secondary CT

Measurement Category III

Note: All CTs used with the product

200 A primary CT

 

must be UL recognized/listed.

Meter burden: 4.04 ohms

 

 

 

 

CT burden: 20 ohms

 

 

Part number: METSECT80200

 

 

Note: All CTs used with the product

 

 

must be UL recognized/listed.

 

 

 

Measurement accuracy

ANSI C12.20 Class 0.5

ANSI C12.20 Class 0.5

(Accuracy compliant when used

IEC 62053-22 Class 0.5S

IEC 62053-22 Class 0.5S

with 0.3% CTs)

 

Measurement Canada Approved

 

 

EG07 compliant

 

 

 

Pulse inputs 1 and 2

Dry form A and solid-state form A

Dry form A and solid-state form A

 

compatible

compatible

 

Internal 3.3 V pull-up

Internal 3.3 V pull-up

 

Maximum frequency 10 Hz

Maximum frequency 10 Hz

 

Minimum pulse width 20 ms

Minimum pulse width 20 ms

 

 

 

Non-volatile memory storage

120 days in 15-minute intervals

120 days in 15-minute intervals

 

 

 

Onboard Ethernet port

10/100 Mb/s

10/100 Mb/s

 

 

 

Onboard Modbus RTU serial port

RS422 or RS485 19200/9600 Baud

RS422 or RS485 19200/9600 Baud

 

 

 

Fuse rating (F1)

North America:120V: T125 mA, 250V

North America:120V: T125 mA, 250V

 

 

 

Environmental

 

 

 

 

 

Operating temperature

-40 to 70oC

-40 to 70oC

Operating humidity

5% to 90% non-condensing

5% to 90% non-condensing

 

 

 

Usage environment

Indoor or enclosed outdoor environment

Indoor or enclosed outdoor environment

 

 

 

Maximum altitude

9843 ft (3000 m)

9843 ft (3000 m)

 

 

 

Pollution degree

2

2

 

 

 

Installation Category

II

II

 

 

 

Measurement Category

III

III

 

 

 

2

©2013 Schneider Electric All Rights Reserved

Image 10
Contents PowerLogicTM Series EM4000 Page Important Information Please noteFCC Part 15 Notice FCC Part 68 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved Introduction PowerLogic EM4000 series System SpecificationsSystem Description PowerLogic EM4000 series meter specifications PowerLogic EM4080 front panel Front Panel DisplayPowerLogic EM4033 and PowerLogic EM4080 internal view Safety Precautions Electrical Standards CompliancePre-Installation Checklist InstallationPre-Installation ReceivingAccess to Power and Lighting Installation ProceduresMounting the PowerLogic EM4000 meter 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved Delta service metering PowerLogic EM4000 meter three-phase Delta service connectionInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Steps Shows a 5A CT connected to the converterPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Ethernet Cable Connecting the CommunicationsConnecting the Modbus RTU Communications Manually Testing Communications Connecting Pulse InputsStart-Up Sequence Diagnostics Mode Normal ModeDisplay Navigation Recording the Meter Map Installation Record sample shown Maintenance Fuse ReplacementEquipment servicing and access Regulatory ComplianceGraphical symbols that appear on equipment Index NumericsPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric