Schneider Electric EM4000 manual Connecting the Communications, Connecting the Ethernet Cable

Page 33

930-134-01-A.00

PowerLogicTM Series EM4000

11/2013

Installation Guide

 

 

Connecting the Communications

Connections for communications using the Ethernet port or Modbus RTU port are described in this section.

Connecting the Ethernet Cable

If the Ethernet port is used to report data, an RJ45 patch cable is required to connect the Ethernet port to the local Ethernet network.

1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.

2. If the local network automatically assigns IP addresses through a DHCP server, the PowerLogic EM4000 meter will be able to report using its factory default IP settings. If the local network is configured for static IP addresses, refer to the PowerLogic EM4000 meter Configuration Guide for instructions on how to configure default static IP addresses.

Connecting the Modbus RTU Communications

If the Modbus port is used to report data, an RS422/RS485 serial cable is required to connect the Modbus RTU port to the local Modbus network.

1. Route the cable through the slot in the PowerLogic EM4000 meter enclosure.

2. Depending on the position of the PowerLogic EM4000 meter in the Modbus network as shown in Figure 13, set the DIP switches as follows:

PowerLogic meter location

S1

S2

S3

S4

Head end

On

Off

Off

Off

Intermediate

Off

Off

Off

Off

Tail end

On

On

On

Off

 

 

 

 

 

3.Refer to the PowerLogic meter Configuration Guide for instructions on how to configure the baud rate, parity settings, and Modbus base address for the RS485 RTU communications.

Figure 13: Modbus wiring diagram

©2013 Schneider Electric All Rights Reserved

25

Image 33
Contents PowerLogicTM Series EM4000 Page Please note Important InformationFCC Part 68 Notice FCC Part 15 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved PowerLogic EM4000 series System Specifications IntroductionSystem Description PowerLogic EM4000 series meter specifications Front Panel Display PowerLogic EM4080 front panelPowerLogic EM4033 and PowerLogic EM4080 internal view Electrical Standards Compliance Safety PrecautionsPre-Installation InstallationPre-Installation Checklist ReceivingInstallation Procedures Access to Power and LightingMounting the PowerLogic EM4000 meter 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved PowerLogic EM4000 meter three-phase Delta service connection Delta service meteringInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Shows a 5A CT connected to the converter StepsPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Communications Connecting the Ethernet CableConnecting the Modbus RTU Communications Connecting Pulse Inputs Manually Testing CommunicationsStart-Up Sequence Normal Mode Diagnostics ModeDisplay Navigation Recording the Meter Map Installation Record sample shown Fuse Replacement MaintenanceRegulatory Compliance Equipment servicing and accessGraphical symbols that appear on equipment Numerics IndexPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric