Schneider Electric EM4000 manual Installing the Current Transformers

Page 26

PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

Installing the Current Transformers

The two models of PowerLogic EM4000 meter use current transformers (CTs) with different secondary outputs. The PowerLogic EM4033 meter uses split-core 0.333V CTs (see Figure 10), and the PowerLogic EM4080 meter uses 80mA CTs only (see Figure 11) and is typically used where accuracy is important and long secondary CT wiring is required (up to 300 feet [91.44 meters]). The PowerLogic EM4080 meter can also use a 5A CT if a 5A converter has first been installed.

For instructions, see “Installing the CTs on the PowerLogic EM4033 and PowerLogic EM4080” on page 20, and “Installing 5A Converters and CTs on the PowerLogic EM4080” on page 21.

Current transformers connect to the PowerLogic EM4033 and PowerLogic EM4080 meters through the 50-conductor CT cable provided with the meter. Table 2 describes the CT wire pairs and the cable color scheme for each meter point. You can also find this information on the inside of the meter’s outer cover.

Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice connectors to attach the CT to a specific meter wire pair. The direction of the energy flow is indicated on the CT by: a label (“This side towards source”); an arrow that points away from the source; or a stamp/label indicating which side is H1 (H1 side faces toward the source).

CT shorting blocks are recommended for all CT installations. CTs measuring live current must either be connected to the PowerLogic meter via the 25-pair CT cable, or the secondary output of the CTs must be shorted together. Open-circuit CTs may generate a hazardous voltage and could damage equipment or cause personal injury.

18

©2013 Schneider Electric All Rights Reserved

Image 26
Contents PowerLogicTM Series EM4000 Page Important Information Please noteFCC Part 15 Notice FCC Part 68 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved System Description PowerLogic EM4000 series System SpecificationsIntroduction PowerLogic EM4000 series meter specifications PowerLogic EM4080 front panel Front Panel DisplayPowerLogic EM4033 and PowerLogic EM4080 internal view Safety Precautions Electrical Standards CompliancePre-Installation Checklist InstallationPre-Installation ReceivingMounting the PowerLogic EM4000 meter Installation ProceduresAccess to Power and Lighting 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved Delta service metering PowerLogic EM4000 meter three-phase Delta service connectionInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Steps Shows a 5A CT connected to the converterPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Modbus RTU Communications Connecting the CommunicationsConnecting the Ethernet Cable Start-Up Sequence Connecting Pulse InputsManually Testing Communications Display Navigation Normal ModeDiagnostics Mode Recording the Meter Map Installation Record sample shown Maintenance Fuse ReplacementEquipment servicing and access Regulatory ComplianceGraphical symbols that appear on equipment Index NumericsPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric