Schneider Electric EM4000 manual Schneider Electric All Rights Reserved

Page 22

PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

For a 208Y/120V three-phase wye panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

Install power supply shorting jumpers (see Figure 6)

Figure 6: PowerLogic EM4000 meter 208Y/120V three-phase wye service connection

2

3

4

5

1

8

7

9

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3)

7 Neutral (white)

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

14

©2013 Schneider Electric All Rights Reserved

Image 22
Contents PowerLogicTM Series EM4000 Page Important Information Please noteFCC Part 15 Notice FCC Part 68 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved Introduction PowerLogic EM4000 series System SpecificationsSystem Description PowerLogic EM4000 series meter specifications PowerLogic EM4080 front panel Front Panel DisplayPowerLogic EM4033 and PowerLogic EM4080 internal view Safety Precautions Electrical Standards CompliancePre-Installation Checklist InstallationPre-Installation ReceivingAccess to Power and Lighting Installation ProceduresMounting the PowerLogic EM4000 meter 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved Delta service metering PowerLogic EM4000 meter three-phase Delta service connectionInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Steps Shows a 5A CT connected to the converterPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Ethernet Cable Connecting the CommunicationsConnecting the Modbus RTU Communications Manually Testing Communications Connecting Pulse InputsStart-Up Sequence Diagnostics Mode Normal ModeDisplay Navigation Recording the Meter Map Installation Record sample shown Maintenance Fuse ReplacementEquipment servicing and access Regulatory ComplianceGraphical symbols that appear on equipment Index NumericsPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric