Schneider Electric EM4000 manual Delta service metering

Page 25

930-134-01-A.00

PowerLogicTM Series EM4000

11/2013

Installation Guide

 

 

Delta service metering

To use the PowerLogic EM4000 meter in a Delta service, the line-to-line voltage from the Delta service must be reduced to 120V line-to-line using appropriate potential transformers. Metering a Delta service requires only two potential transformers, and only two CTs for phase A and C.

For a three-phase Delta panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to meter terminal B (black wire)

Connect earth wire to earth post using lug provided (see Figure 9)

Figure 9: PowerLogic EM4000 meter three-phase Delta service connection

2

1

9

3

 

 

4

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

7

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3) 7 J3-B to J3-N shorting wire

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

©2013 Schneider Electric All Rights Reserved

17

Image 25
Contents PowerLogicTM Series EM4000 Page Please note Important InformationFCC Part 68 Notice FCC Part 15 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved Introduction PowerLogic EM4000 series System SpecificationsSystem Description PowerLogic EM4000 series meter specifications Front Panel Display PowerLogic EM4080 front panelPowerLogic EM4033 and PowerLogic EM4080 internal view Electrical Standards Compliance Safety PrecautionsPre-Installation InstallationPre-Installation Checklist ReceivingAccess to Power and Lighting Installation ProceduresMounting the PowerLogic EM4000 meter 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved PowerLogic EM4000 meter three-phase Delta service connection Delta service meteringInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Shows a 5A CT connected to the converter StepsPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Ethernet Cable Connecting the CommunicationsConnecting the Modbus RTU Communications Manually Testing Communications Connecting Pulse InputsStart-Up Sequence Diagnostics Mode Normal ModeDisplay Navigation Recording the Meter Map Installation Record sample shown Fuse Replacement MaintenanceRegulatory Compliance Equipment servicing and accessGraphical symbols that appear on equipment Numerics IndexPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric