PowerLogicTM Series EM4000 | |
11/2013 | Installation Guide |
|
|
Introduction
This document describes the PowerLogic EM4033 and EM4080 meters, including procedures to install and start up the unit, and complete the initial configuration:
•“System Description” on page 1
•
•“Installation Procedures” on page 7
•“Connecting Pulse Inputs” on page 26
•“Fuse Replacement” on page 30
This documentation is intended for those responsible for installing and configuring the PowerLogic EM4033 and EM4080 meters. Installers must be qualified electricians with knowledge of local and national code requirements. See “Safety Precautions” on page 5.
System Description
The PowerLogic EM4033 and EM4080 meters support:
•
•
•
Depending on how the meters are installed and configured, they can meter 8, 12, or 24 individual meter points. The PowerLogic EM4033 and EM4080 meters are designed for residential, commercial, and industrial use and display the power and consumption readings for each measurement point.
PowerLogic EM4000 series System Specifications
The PowerLogic EM4000 series system architecture includes:
•
•2 control voltage variants: 120V 60Hz and 277V 60Hz
•120/208V, 120/240V and 277/480V configurations, and 347/600V with external potential transformers
•up to 8, 12, or 24 individual meter points
•local Ethernet configuration interface via PC and web browser
•Ethernet port for remote reporting
•Modbus RTU serial port, for remote reporting
•serial port for remote display
•2 pulse inputs to connect metering devices
Table 1 lists the system specifications of the PowerLogic EM4033 and EM4080 meters.
©2013 Schneider Electric All Rights Reserved | 1 |