PowerLogicTM Series EM4000 |
|
Installation Guide | 11/2013 |
|
|
For a 600Y/347V or higher
•Connect meter terminal A to the voltage disconnect phase A (red wire)
•Connect meter terminal B to the voltage disconnect phase B (black wire)
•Connect meter terminal C to the voltage disconnect phase C (blue wire)
•Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)
•Connect earth wire to earth post using lug provided
•Install power supply shorting jumpers (see Figure 8)
NOTE: For the wiring of the potential transformers, see Figure 4.
Figure 8: PowerLogic EM4000 meter 600Y/347V or higher three-phase wye service with potential transformers connection
2 | 3 | 4 | 5 |
1
8
7
9 | 6 |
Legend:
1BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9
16 | ©2013 Schneider Electric All Rights Reserved |