Page 30

PowerLogicTM Series EM4000

930-134-01-A.00

Installation Guide

11/2013

 

 

 

To connect the 5A CT to the converter on the PowerLogic EM4080, follow these

 

steps:

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Turn off all power supplying this equipment before working on or inside the equipment.

Always use a properly rated voltage sensing device to confirm the power is off.

NEVER open circuit a CT; use the shorting block to short circuit the leads of the CT before removing the connection from the meter.

Do not crimp the insulation when making the wire connections.

Failure to follow these instructions will result in death or serious injury.

1.Connect the X1 lead of the 5A CT to the shorting device.

2.Connect the X2 lead of the 5A CT to the shorting device.

3.Connect the X1 lead (red) from the 5A side of the converter to the CT X1 lead on the shorting device.

4.Connect the X2 lead (black) from the 5A side of the converter to the CT X2 lead on the shorting device.

5.Connect the X1 lead (white) from the 80mA side of the converter to the X1 lead within the 25 pair cable for the selected meter point ID listed in Table 2.

6.Connect the X2 lead (black) from the 80mA side of the converter to the X2 lead within the 25 pair cable for the selected meter point ID listed in Table 2

Figure 12 shows a 5A CT connected to the converter.

22

©2013 Schneider Electric All Rights Reserved

Image 30
Contents PowerLogicTM Series EM4000 Page Important Information Please noteFCC Part 15 Notice FCC Part 68 NoticeNetwork Compatibility Notice for the Internal Modem Page Table of Contents Schneider Electric All Rights Reserved PowerLogic EM4000 series System Specifications IntroductionSystem Description PowerLogic EM4000 series meter specifications PowerLogic EM4080 front panel Front Panel DisplayPowerLogic EM4033 and PowerLogic EM4080 internal view Safety Precautions Electrical Standards CompliancePre-Installation Checklist InstallationPre-Installation ReceivingInstallation Procedures Access to Power and LightingMounting the PowerLogic EM4000 meter 11.0 27.9 cm EM4033 11/2013 Installation Guide Shorting block detail 930-134-01-A.00 Hazard of Electric SHOCK, EXPLOSION, or ARC Flash For a single-phase panel with the 120V variant of the meter Schneider Electric All Rights Reserved From Panel Schneider Electric All Rights Reserved Delta service metering PowerLogic EM4000 meter three-phase Delta service connectionInstalling the Current Transformers PowerLogic EM4033 split-core 0.333V current transformer Source Installing 5A Converters and CTs on the PowerLogic EM4080 Steps Shows a 5A CT connected to the converterPowerLogic EM4080 5A CT connection to converter PowerLogic EM4000 meter CT color pair identification Connecting the Communications Connecting the Ethernet CableConnecting the Modbus RTU Communications Connecting Pulse Inputs Manually Testing CommunicationsStart-Up Sequence Normal Mode Diagnostics ModeDisplay Navigation Recording the Meter Map Installation Record sample shown Maintenance Fuse ReplacementEquipment servicing and access Regulatory ComplianceGraphical symbols that appear on equipment Index NumericsPowerLogicTM EM4000 Series 930-134-01-A.00 Index 11/2013 Page Schneider Electric