Cooper Lighting ELPS502 manual Periodic Testing, Complete Installation

Page 4

WARNING

To avoid electrical shocks, use fixture only on systems with an equipment grounding conductor.

NOTE

In Class II and Class III and Simultaneous Presence locations, limit upward aiming of fixture to a maximum of 30º above horizontal. Greater upward aiming could lead to excessive dust buildup and dangerous overheating of the dust.

NOTE

Unit needs to charge for 72 hours before conducting any tests. Do not disconnect AC power until unit is fully charged.

3.Test wiring for correctness with continuity checks and also for unwanted grounds with insulation resistance tester.

4.Allow the ELPS to charge under line power for 72 hours before initiating any testing of the emergency operation of the lights.

D. Complete Installation

1.Install CID101 corrosion inhibitor device (supplied loose in ELPS50). Recommended location is on the bottom wall between “Main Power On” pilot light and 1" NPT tapped hole. Refer to CID101 instructions for installation.

CAUTION

To avoid explosion, clean both flat joint surfaces of body and cover before closing. Dirt or foreign material must not accumulate on flat joint surfaces. Surfaces must seat fully against each other to provide a proper explosion proof seal.

Figure 5. ELPS50 Controls

2.Close cover and securely tighten all cover bolts and nuts to 30 ft. lbs. torque making certain that no cover bolts are omitted. Use only bolts supplied with the enclosure.

NOTE: ELPS units have two stud bolts located at diagonally opposite corners of the body to aid in positioning cover.

NOTE

A Class I, Division 1 sealing fitting must be installed within 18 inches of the conduit entry of the ELPS enclosure. Use Chico A or Chico SpeedSeal sealing compound to seal the conduit entry.

DO NOT depress the push-to-test pushbutton until after the ELPS has been powered for 72 hours. The emergency battery requires 72 hours to fully charge. The indicating light will illuminate steadily (no pulsing) when the ELPS is fully charged.

3.Test emergency lighting system for proper operation:

a.Turn on power to designated disconnect switch.

b.Turn on designated disconnect switch and observe:

“Main Power ON” indicating pilot light should be operating.

EVLA12 emergency light(s) should be “OFF”.

c.Press “Push-to-Test” indicating push button switch and observe:

“Main Power ON” light should be “OFF”.

EVLA12 emergency light(s) should be “ON”.

4.Lock designated disconnect switch “ON” to prevent unauthorized persons from turning system “OFF”.

5.Adjust EVLA12 emergency light(s) for the desired direction of illumination & lock into position using 1-5/8” open-ended wrench & torquing to 58 lb.-ft. See Figure 2.

E. Remote Mounting EVLA12 Emergency Light Only

1.Attach the EVLA12 to a Cooper Crouse-Hinds EABC36 or EABL36 1" NPT outlet box.

2.Secure this assembly to the mounting surface with ¼ inch bolts or lag screws of the required length (not supplied).

3.Refer to Table 1 on page 6 for conductor recommendations.

4.Refer to Sections B for aiming adjustments and section C for Conduit Connections and Wiring.

PERIODIC TESTING

Article 700 of the National Electrical Code states that, “Systems shall be tested periodically on a schedule acceptable to the authority having jurisdiction to assure their maintenance in proper operating condition”. It also states that, “A written record shall be kept of such tests and maintenance”.

In the absence of periodic testing requirements by a local authority, the following recommendations from the NFPA 101 (2003) Life Safety Code are strongly recommended:

1.Monthly: Operate “Push-to-Test” switch and keep depressed for a minimum of 30 seconds. Observe that emergency lighting fixtures are on full brightness for the full time. Record the test on the maintenance record card. Maintenance Record Card is provided in instruction sheet envelope.

2.Annually: Shut off power at the distribution panel. Verify that the emergency lighting fixtures remain “ON” for a minimum of 1-1/2 hours.

NOTE: Leave the designated disconnect switch “ON” during this test so that battery circuit is not interrupted. We suggest that this test be continued until the power supply automatically shuts the emergency light(s) off. This will help maintain full battery capacity.

Record the test on the Maintenance Record Card.

Allow 48 hours charging time before depending on the battery to operate at full capacity.

Failure to function properly in either test may indicate the need for battery or lamp replacement.

IF 1510 • 05/06

Copyright © 2006, Cooper Industries, Inc.

Page 4

Image 4
Contents Application RatingsDetail indication logic is given below EVLA12Installation Install ELPS502 System or ELPS50 Power SupplyAttach and Adjust EVLA12 Lighting Fixtures ELPS50 Power Supply= 220/240 = L Conduit Connection and Wiring= Batt + = L + Complete Installation Periodic TestingRemote Mounting EVLA12 Emergency Light Only Battery Replacement Fixture Lamp ReplacementExit Sign Lamp Replacement Pilot Light Lamp ReplacementReplacement Circuit Board & Battery KIT MaintenanceBreather and Drain = GRD = 220/240Connect AC Power and Test System Time Delay FeatureTroubleshooting Guide Wire Sizing for Remote InstallationNfpa 101 2003 Requirements Elps EVI Emergency Lighting Fixture Exit SignElps EVA GB Emergency Lighting Fixture GB Group B Exit Sign 30 SECClassification AvertissementDEL éteinte Charge complèteMise EN Garde RemarqueFixation et réglage du ou des luminaires EVLA12 Raccord de conduite et câblage Schéma de câblageAchèvement de linstallation Essai RégulierRemplacement DE LA Pile Remplacement DE Lampoule DE Lenseigne DE SortieRemplacement DE Lampoule DU Luminaire Remplacement DE Lampoule DE LA Lampe TémoinEntretien Reniflard ET PurgeLA Trousse ELPS-K50 Comprend DEL illuminé sans clignotements Charge complèteCalibre de fil pour une installation à distance Rebrancher Lalimentation Secteur ET Tester LE SystèmeCaractéristique DE Délai Dinterruption Guide DE DépannageFiche Dentretien Spécifications DE LA Nfpa 101Aplicación EspecificacionesImportante PrecauciónNota InstalaciónFije y ajuste el o los Accesorios de Iluminación EVLA12 Conexión de conductos y cableado = Batt += L + = Batt Vea la nota de Precaución más abajoComplete la instalación Pruebas PeriódicasMontaje remoto de la Luz de Emergencia EVLA12 únicamente Reemplazo DE LA Batería Reemplazo DE Lalámparade Laseñal DE SalidaReemplazo DE LA Lámpara DEL Accesorio Reemplazo DE LA Lámpara PilotoConfigure el interruptor de desconexión designado en OFF ReemplazodelaplacadecircuitosyelkitdebateríaMantenimiento Respiradero Y DrenajeGuía DE Solución DE Problemas Conecte LA Energía AC Y Pruebe EL SistemaFunción DE Temporización TablaSeñal DE Salida GB Grupo B Requisitos Nfpa 101Fecha 30 1-1/2