MAINTENANCE RECORD

NFPA 101 (2003) REQUIREMENTS

"A FUNCTIONAL TEST SHALL BE CONDUCTED ON EVERY REQUIRED EMERGENCY LIGHTING SYSTEM AT 30-DAY INTERVALS FOR A MINIMUM OF 30 SECONDS. AN ANNUAL TEST SHALL BE CONDUCTED FOR THE 1-1/2 HOUR DURATION.

EQUIPMENT SHALL BE FULLY OPERATIONAL FOR THE DURATION OF THE TEST. WRITTEN RECORDS OF TESTING SHALL BE KEPT BY THE OWNER FOR INSPECTION BY THE AUTHORITY HAVING JURISDICTION."

EVLA EMERGENCY LIGHTING FIXTURE

ELPS EMERGENCY LIGHTING POWER SUPPLY

ELPS EVI EMERGENCY LIGHTING FIXTURE (EXIT SIGN)

ELPS EVA GB EMERGENCY LIGHTING FIXTURE (GB [Group B] EXIT SIGN)

SEE INSTALLATION AND MAINTENANCE

INSTRUCTION SHEETS FOR METHODS OF TESTING

 

 

DURATION OF TEST

 

 

 

 

 

DATE

30 SEC

1-1/2

OTHER

BATTERY

INSPECTED

LAMP REPLACED

NOTES

 

 

 

HOUR

 

REPLACED

BY

(RECORD FIXTURE LOCATION)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale”, and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

Cooper Industries Inc.

IF 1510

Crouse-Hinds Division

Revision 1

PO Box 4999, Syracuse, New York 13221 • U.S.A.

New 05/06

Copyright © 2006, Cooper Industries, Inc.

 

Image 8
Contents Application RatingsDetail indication logic is given below EVLA12Installation Install ELPS502 System or ELPS50 Power SupplyAttach and Adjust EVLA12 Lighting Fixtures ELPS50 Power Supply= Batt + = L + Conduit Connection and Wiring= 220/240 = L Remote Mounting EVLA12 Emergency Light Only Periodic TestingComplete Installation Battery Replacement Fixture Lamp ReplacementExit Sign Lamp Replacement Pilot Light Lamp ReplacementReplacement Circuit Board & Battery KIT MaintenanceBreather and Drain = GRD = 220/240Connect AC Power and Test System Time Delay FeatureTroubleshooting Guide Wire Sizing for Remote InstallationNfpa 101 2003 Requirements Elps EVI Emergency Lighting Fixture Exit SignElps EVA GB Emergency Lighting Fixture GB Group B Exit Sign 30 SECClassification AvertissementDEL éteinte Charge complèteFixation et réglage du ou des luminaires EVLA12 RemarqueMise EN Garde Raccord de conduite et câblage Schéma de câblageAchèvement de linstallation Essai RégulierRemplacement DE LA Pile Remplacement DE Lampoule DE Lenseigne DE SortieRemplacement DE Lampoule DU Luminaire Remplacement DE Lampoule DE LA Lampe TémoinEntretien Reniflard ET PurgeLA Trousse ELPS-K50 Comprend DEL illuminé sans clignotements Charge complèteCalibre de fil pour une installation à distance Rebrancher Lalimentation Secteur ET Tester LE SystèmeCaractéristique DE Délai Dinterruption Guide DE DépannageFiche Dentretien Spécifications DE LA Nfpa 101Aplicación EspecificacionesImportante PrecauciónFije y ajuste el o los Accesorios de Iluminación EVLA12 InstalaciónNota Conexión de conductos y cableado = Batt += L + = Batt Vea la nota de Precaución más abajoMontaje remoto de la Luz de Emergencia EVLA12 únicamente Pruebas PeriódicasComplete la instalación Reemplazo DE LA Batería Reemplazo DE Lalámparade Laseñal DE SalidaReemplazo DE LA Lámpara DEL Accesorio Reemplazo DE LA Lámpara PilotoConfigure el interruptor de desconexión designado en OFF ReemplazodelaplacadecircuitosyelkitdebateríaMantenimiento Respiradero Y DrenajeGuía DE Solución DE Problemas Conecte LA Energía AC Y Pruebe EL SistemaFunción DE Temporización TablaFecha 30 1-1/2 Requisitos Nfpa 101Señal DE Salida GB Grupo B