Cooper Lighting manual Installation, Install ELPS502 System or ELPS50 Power Supply

Page 2

INSTALLATION

A. Install ELPS502 System or ELPS50 Power Supply

WARNING

To avoid electrical shock, electrical power must be turned OFF before and during installation and maintenance.

30.00EXS/EXD

30.63EXD GB

33.00 EXS/EXD

 

35.63 EXD GB

6.50

 

1.13 EXS/EXD

2.13 EXD GB

7.00 EXS/EXD

8.38 EXD GB

29.63

11.00

 

12.81

11.13

14.75

16.50

 

Figure 1. ELPS502 and ELPS502 EXS / EXD Dimensions

1. Select mounting location that will provide suitable strength and rigidity for supporting

1. Remove pipe plug(s) from the 1" NPT tapped holes in the side(s) of the ELPS50

power supply and attached lighting fixtures. Figure 1 shows the overall dimensions

power supply enclosure where the EVLA12 fixture is to be installed.

and mounting dimensions for the four mounting feet.

NOTE: Remotely mounted EVLA fixtures can be mounted in a suitable splice box,

 

Weights:

ELPS502 System

50 lbs.

 

ELPS502 EXS/EXD System

60 lbs.

 

ELPS50 Power Supply

40 lbs.

 

EVLA12 Fixture

5 lbs.

2.Securely fasten enclosure to the mounting location using 3/8" diameter bolts or screws.

IMPORTANT

The recommended mounting position is with the back wall of the enclosure fastened to a vertical surface with the pilot light and push-to-test push button located on the bottom of the enclosure.

NOTE

A Class I, Division 1 sealing fitting must be installed within 18 inches of the conduit entry of the ELPS enclosure. Use Chico A or Chico SpeedSeal sealing compound to seal the conduit entry.

3.Remove the cover bolts and nuts from two stud bolts, then lift off cover and carefully set it aside to prevent damage to the flat joint and flange gasket.

NOTE: ELPS units have two stud bolts located at diagonally opposite corners of the body to aid in positioning cover. Do not remove stud bolts.

4. Proceed to Section B to attach and/or adjust EVLA lighting fixtures.

CAUTION

To avoid damaging the flat joint surfaces, do not use hammers or prying tools to open covers. Do not handle covers roughly, or place them on surfaces that might damage or scratch the flat joint surfaces.

B. Attach and Adjust EVLA12 Lighting Fixture(s)

NOTE: If installing ELPS502, fixtures are already attached. Proceed to Step 5 to adjust fixtures.

CAUTION

such as Crouse-Hinds EABT36, EABL36, or EABC36 that provides a 1" hub for fixture attachment.

IMPORTANT

Spacers are required between splice box and mounting surface to ensure proper clearance for fixture hub rotation during installation. 11/8” dimension is required between center line of mounting hub & face of mounting surface.

2.Thread light assembly into body being sure that the reducer fitting is engaged with the body at least five full threads.

3.Using a 1-5/8” wrench, loosen Nut ‘A’, position lamp head in desired vertical position and retighten to 58 lb.-ft. torque.

4.Using the same 1-5/8” wrench, loosen Nut ‘B’ and position lamp head in desired horizontal position. Be sure to re-tighten Nut ‘B’ to 58 lb.-ft. torque.

Nut ‘B’

Nut ‘A’

Figure 2. EVLA Lighting Fixture

EVLA fixture head and arm are limited to no more than 180º of rotational adjustment. Failure to adhere to this will result in damage to the internal wiring.

IF 1510 • 05/06

Copyright © 2006, Cooper Industries, Inc.

Page 2

Image 2
Contents Detail indication logic is given below ApplicationRatings EVLA12Attach and Adjust EVLA12 Lighting Fixtures InstallationInstall ELPS502 System or ELPS50 Power Supply ELPS50 Power Supply= Batt + = L + Conduit Connection and Wiring= 220/240 = L Remote Mounting EVLA12 Emergency Light Only Periodic TestingComplete Installation Exit Sign Lamp Replacement Battery ReplacementFixture Lamp Replacement Pilot Light Lamp ReplacementBreather and Drain Replacement Circuit Board & Battery KITMaintenance = GRD = 220/240Troubleshooting Guide Connect AC Power and Test SystemTime Delay Feature Wire Sizing for Remote InstallationElps EVA GB Emergency Lighting Fixture GB Group B Exit Sign Nfpa 101 2003 RequirementsElps EVI Emergency Lighting Fixture Exit Sign 30 SECDEL éteinte ClassificationAvertissement Charge complèteFixation et réglage du ou des luminaires EVLA12 RemarqueMise EN Garde Raccord de conduite et câblage Schéma de câblageAchèvement de linstallation Essai RégulierRemplacement DE Lampoule DU Luminaire Remplacement DE LA PileRemplacement DE Lampoule DE Lenseigne DE Sortie Remplacement DE Lampoule DE LA Lampe TémoinLA Trousse ELPS-K50 Comprend EntretienReniflard ET Purge DEL illuminé sans clignotements Charge complèteCaractéristique DE Délai Dinterruption Calibre de fil pour une installation à distanceRebrancher Lalimentation Secteur ET Tester LE Système Guide DE DépannageFiche Dentretien Spécifications DE LA Nfpa 101Importante AplicaciónEspecificaciones PrecauciónFije y ajuste el o los Accesorios de Iluminación EVLA12 InstalaciónNota = L + = Batt Conexión de conductos y cableado= Batt + Vea la nota de Precaución más abajoMontaje remoto de la Luz de Emergencia EVLA12 únicamente Pruebas PeriódicasComplete la instalación Reemplazo DE LA Lámpara DEL Accesorio Reemplazo DE LA BateríaReemplazo DE Lalámparade Laseñal DE Salida Reemplazo DE LA Lámpara PilotoMantenimiento Configure el interruptor de desconexión designado en OFFReemplazodelaplacadecircuitosyelkitdebatería Respiradero Y DrenajeFunción DE Temporización Guía DE Solución DE ProblemasConecte LA Energía AC Y Pruebe EL Sistema TablaFecha 30 1-1/2 Requisitos Nfpa 101Señal DE Salida GB Grupo B