Cooper Lighting ELPS502 Replacement Circuit Board & Battery KIT, Maintenance, Breather and Drain

Page 6

REPLACEMENT CIRCUIT BOARD & BATTERY KIT

ELPS-K50 KIT CONSISTS OF:

(1)Circuit Board & Charger Assembly with Mounting Bracket

(1)IF- 1510-A Instructions

(1)Sealed Ni-CAD Battery

(1)2 Volt LED for Pilot Light

(1)CID101 Corrosion Inhibitor Device

This kit includes a new, LED indicating lamp that gives a visual status of the unit. Details indicating LED logic is given below:

NOTE

ELPS series emergency light fixtures were re-designed in October, 2005. Previous models had circuit boards wired to normally closed contacts. This ELPS-K50 kit has a new circuit board that must be wired to normally open contacts. Older units used different style light fixture heads (see Figure 8 below).

 

No Light

AC power is removed from circuit

Steady Light (No blinks)

Fully Charged

Light Blinks Once

Charging

• - •

Light Blinks Twice

Battery Failure

• - • - •

Light Blinks Three Times

Circuit Failure

Immediately after supply power is initiated the indicating lamp will blink/pulse to indicate that the unit is charging. Once installed with supply power, the ELPS requires 72 hours to charge the battery. Once the unit has completed charging, the indicating light will stop blinking and go to steady. Every six months, the unit will automatically perform a 90- minute battery discharge test.

At the completion of the test, if it is determined not to have met the 90 minute requirement, the indicating lamp will display circuit failure (3 blinks). At any time, if the battery connection is not adequate the indicating lamp will display a battery failure (2 blinks).

WARNING

To prevent injury from electric shock, all power must be removed from the fixture during maintenance.

WARNING

Even after disconnect, batteries will still be live. To prevent electrical shock and explosion, take extra care not to touch leads together or to ground.

MAINTENANCE

WARNING

To avoid explosion always disconnect primary power source using designated disconnect switch before opening enclosure for inspection or service.

1.Conduct periodic testing in accordance with local authority and Periodic Testing section of these instructions.

2.Clean fixture lens and exterior surfaces periodically. We recommend every three months or more frequently if appropriate.

3.Frequent interior inspection should be made. A schedule for maintenance check should be determined by the environment and frequency of use. It is recommended that it should be at least once a year.

4.Perform visual, electrical, and mechanical checks on all components on a regular basis.

Visually check for undue heating evidenced by discoloration of wires or other components, damage or worn parts, or leakage evidence by

water or corrosion in the interior.

Electrically check to make sure that all connections are clean and tight.

Mechanically check that all parts are properly assembled.

5.Do not attempt field replacement or repair of ELPS50 Power Supply cover gasket. Instead, remove damaged gasket and continue to use cover without gasket. This will assure safety for use in Class I and Class II hazardous (classified) locations. However, the enclosure will not be rain tight.

CAUTION

To avoid explosion, clean both flat joint surfaces of body and cover before closing. Dirt or foreign material must not accumulate on flat joint surfaces. Surfaces must seat fully against each other to provide a proper explosion proof seal.

BREATHER AND DRAIN

ELPS50 power supply enclose is provided with breather and drain. Refer to Installation and Maintenance Information IF-843 for inspection and maintenance instructions.

IMPORTANT

A DESIGNATED DISCONNECT SWITCH IS REQUIRED FOR SAFETY, TO POWER THE ELPS502 EMERGENCY LIGHT SYSTEM AND CHARGE THE BATTERIES.

To avoid explosion, a Designated Disconnect switch with lock-in/lock-out capability is required for safe servicing of the completely wired unit. The lock- in/lock-out capability will prevent unauthorized opening of the circuit when the system should be functioning and to help prevent energizing of the system while it is being serviced, minimizing the possibility of arcing in the battery circuit while the enclosure is open in a hazardous (classified) area.

Units supplied with option S794 or Option S854 already have a disconnect switch installed on the enclosure. Standard units require a remote disconnect switch. If the switch is also located in a hazardous area, you must install a Class 1, Div. 1, rated switch. Use Crouse-Hinds EDS2129 or EDS2129-GB (for Group B applications).

 

 

 

 

YELLOW - AMARILLO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YELLOW - AMARILLO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE - AZUL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE - AZUL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

-

L+

 

 

 

 

 

RED-ROJO

YELLOW-AMARILLO

RED -ROJO

ORANGE - NARANJA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEGRO-BLACK

 

ROJO-RED

BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATERIA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21G03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BROWN - CAFE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK - NEGRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE - BLANCO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

 

 

6

7

8

9

NEGRO

- ROJO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRD

COM

120

220

277

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

127

240

 

 

 

 

 

 

 

 

 

 

 

BLACK-

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN CHARGER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMADOR

 

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRINCIPAL DE

 

BLOCK DE TERMINALES

 

 

 

 

EVLA12'S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CARGA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = GRD

4 = 220/240

 

7 = L -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUTON DE PRUEBA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY DISCONNECT

 

 

 

 

 

 

 

 

 

 

 

 

2 = COM

5 = 277

 

 

 

8 = BATT +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTERRUPTOR

 

 

 

 

 

 

 

 

PILOT LIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAMPARA PILOTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCONECTADOR

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = 120

 

6 = L +

 

9 = BATT -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DE BATERIA

 

 

 

Figure 7. Wiring Diagram

REMOVAL OF EXISTING CIRCUIT ASSEMBLY (For units made BEFORE October, 2005).

1. Disconnect branch AC power at circuit

Figure 8

breaker and lockout.

 

2.Turn "Designated disconnect" switch to "OFF".

3.After removing all AC and DC power to the fixture, remove all cover fasteners to gain access to the interior.

WARNING

To avoid explosion, do not damage the flat joint surfaces. Do not use hammers or prying tools to handle covers. Do not handle covers roughly, or place them on surfaces that might damage or scratch the flat joint surfaces.

4.Disconnect wire leads at the pilot light and switch.

5.Disconnect all incoming connections from terminals GRD (#1) through L- (#7).

6.Remove the mounting stud and pillar located in the uppermost left corner of the interior. Remove the three other hold down nuts and lock washers on the aluminum backplate. Remove the old interior assembly and set aside.

7.Install the new interior assembly using the three remaining hold down nuts and lock washers removed from terminals L+ (#6) and L- (#7).

IF 1510 • 05/06

Copyright © 2006, Cooper Industries, Inc.

Page 6

Image 6
Contents Detail indication logic is given below ApplicationRatings EVLA12Attach and Adjust EVLA12 Lighting Fixtures InstallationInstall ELPS502 System or ELPS50 Power Supply ELPS50 Power SupplyConduit Connection and Wiring = 220/240 = L= Batt + = L + Periodic Testing Complete InstallationRemote Mounting EVLA12 Emergency Light Only Exit Sign Lamp Replacement Battery ReplacementFixture Lamp Replacement Pilot Light Lamp ReplacementBreather and Drain Replacement Circuit Board & Battery KITMaintenance = GRD = 220/240Troubleshooting Guide Connect AC Power and Test SystemTime Delay Feature Wire Sizing for Remote InstallationElps EVA GB Emergency Lighting Fixture GB Group B Exit Sign Nfpa 101 2003 RequirementsElps EVI Emergency Lighting Fixture Exit Sign 30 SECDEL éteinte ClassificationAvertissement Charge complèteRemarque Mise EN GardeFixation et réglage du ou des luminaires EVLA12 Raccord de conduite et câblage Schéma de câblageAchèvement de linstallation Essai RégulierRemplacement DE Lampoule DU Luminaire Remplacement DE LA PileRemplacement DE Lampoule DE Lenseigne DE Sortie Remplacement DE Lampoule DE LA Lampe TémoinLA Trousse ELPS-K50 Comprend EntretienReniflard ET Purge DEL illuminé sans clignotements Charge complèteCaractéristique DE Délai Dinterruption Calibre de fil pour une installation à distanceRebrancher Lalimentation Secteur ET Tester LE Système Guide DE DépannageFiche Dentretien Spécifications DE LA Nfpa 101Importante AplicaciónEspecificaciones PrecauciónInstalación NotaFije y ajuste el o los Accesorios de Iluminación EVLA12 = L + = Batt Conexión de conductos y cableado= Batt + Vea la nota de Precaución más abajoPruebas Periódicas Complete la instalaciónMontaje remoto de la Luz de Emergencia EVLA12 únicamente Reemplazo DE LA Lámpara DEL Accesorio Reemplazo DE LA BateríaReemplazo DE Lalámparade Laseñal DE Salida Reemplazo DE LA Lámpara PilotoMantenimiento Configure el interruptor de desconexión designado en OFFReemplazodelaplacadecircuitosyelkitdebatería Respiradero Y DrenajeFunción DE Temporización Guía DE Solución DE ProblemasConecte LA Energía AC Y Pruebe EL Sistema TablaRequisitos Nfpa 101 Señal DE Salida GB Grupo BFecha 30 1-1/2