Cooper Lighting ELPS502 Battery Replacement, Fixture Lamp Replacement, Exit Sign Lamp Replacement

Page 5

BATTERY REPLACEMENT

1.Turn “designated disconnect” switch to “OFF”.

2.Remove ELPS50 power supply enclosure cover bolts and nuts, then lift off cover and carefully set it aside to prevent damage to the flat joint and flange gasket.

WARNING

To avoid explosion, do not damage the flat joint surfaces. Do not use hammers or prying tools to open covers. Do not handle covers roughly, or place them on surfaces that might damage or scratch the flat joint surfaces.

3.Disconnect battery leads from terminals Batt+ (#8) and Batt- (#9) on terminal block. See Figure 3.

4.Remove the four screws that fasten the battery hold-down bracket to the mounting plate and loosen the retaining screw of one of the battery stop brackets. Remove battery. Retain battery insulating sheet for use with replacement battery.

WARNING

To avoid potential explosion, do not short circuit the battery or connector terminals.

5.Cover replacement battery with insulating sheet and reinstall battery using hold-down bracket and four screws previously removed. Retighten battery stop bracket screw. Reconnect black battery conductor to terminal Batt+ (#8) and red conductor to terminal Batt- (#9).

CAUTION

To avoid exposing battery terminals, insulating sheet must completely cover the battery.

WARNING

To avoid explosion, clean both flat joint surfaces of body and cover before closing. Dirt or foreign material must not accumulate on flat joint surfaces. Surfaces must seat fully against each other to provide a proper explosion proof seal.

6.Close cover and securely tighten all cover bolts and nuts to 30 ft. lbs. torque making certain that no cover bolts are omitted. Use only bolts supplied with enclose.

7.Turn ON supply power to the ELPS Light-Pak and turn ON the battery disconnect switch [S794 or S854] located next to the “Push-To-Test” button.

8.Test replacement battery following Step 4 of “D. Complete Installation”.

WARNING

To avoid explosion:

1.Exercise care in handling cells/batteries in order to prevent shorting of the cell with conductive materials such as rings, bracelets, and keys. The cell or conductor may overheat and cause burns.

2.Do not dispose of the cell/battery in open flame; cells may burst.

3.Do not open or mutilate cell/battery. Opened cells may release corrosive electrolytes which may have harmful effects on the skin and eyes and may be toxic if ingested.

WARNING

To maintain explosionproof integrity, make sure all threads are fully engaged.

8.Slide locking tab into position so it engages one of the slots on the globe assembly. Tighten screw to secure locking tab.

9.Carefully slide EXIT sign back over globe assembly. Attach with 3 screws removed in Step 1

Locking

Screw

FIXTURE LAMP

REPLACEMENT

Figure 6.

CAUTION

To avoid shattering the lamp, protect lamp against scratches and abrasions. Wear protective eyeglasses and clothing when handling lamp. Always allow lamp to cool before removing. Dispose of lamp properly .

1.Turn OFF supply power to the ELPS Light-Pak and turn OFF the battery disconnect switch [S794 or S854] located next to the “Push-To-Test” button.

2.Loosen lens ring locking screw but do not remove. See Figure 6.

3.Remove lens by turning counter-clockwise until all threads are disengaged.

4.Pull lamp straight out of socket and discard.

5.Install replacement lamp, making sure that lamp is free of all fingerprints and soil.

Fixture Lamp: No. 789, Miniature, Tungsten Halogen,

G4, 2-pin, 14 watt.

6.Install lens ring by turning clockwise until threads are fully engaged.

All screw threads have been treated with a corrosion resistant lubricant. Whenever disturbing threaded joints, relubricate the threads with Crouse-Hinds STL thread lubricant.

CAUTION

To avoid damaging threads during installation, exercise care to prevent grit, dirt or other foreign material from lodging on threads. If such foreign material does settle on these threads, clean them with kerosene or Stoddard solvent**, then relubricate with STL thread lubricant.

**To avoid potential explosion, oxidation and corrosion, do not use gasoline or similar solvents.

7Tighten locking screw.

8.Turn ON supply power to the ELPS Light-Pak and turn ON the battery disconnect switch [S794 or S854] located next to the “Push-To-Test” button.

9.Test lamp following Step 4 of “D. Complete Installation”.

EXIT SIGN LAMP REPLACEMENT

For units with optional EXIT signs (suffix “-EXS” or “-EXD”)

1.Remove the three screws holding the EXIT sign to the fixture housing. Carefully remove the EXIT sign by sliding down and away from the light fixture assembly.

2.Loosen the screw that secures the locking tab. Lift tab and retighten screw to hold locking tab temporarily out of the way.

3.Unscrew globe assembly from fixture housing.

4.Remove lamp.

5.Perform cleaning and inspection as necessary.

6.Screw new lamp into lampholder and securely tighten lamp. New lamp must be identical type, size and wattage as marked on the nameplate luminaire. The bulb for the ELPS EXS Exit sign (EVI & EVA) is a Candex 15 Watt, 12 Volt, A15 frosted bulb. The candex item number is A15-15F12V.

PILOT LIGHT LAMP REPLACEMENT

1.Turn OFF supply power to the ELPS Light-Pak and turn OFF the battery disconnect switch [S794 or S854] located next to the “Push-To-Test” button.

2.Unscrew jewel assembly from pilot light.

3.Push lamp in, twist counter-clockwise, then remove lamp and discard.

4.Install replacement pilot light lamp.

Pilot Light : MB444WC1-2VF/N-DP 2V LED with miniature bayonet base *

5.Replace jewel assembly , securely tightening it onto barrel.

6.Turn “ON” designated disconnect switch.

* Available from Starled, Inc. (www.starled.com)

IF 1510 • 05/06

Copyright © 2006, Cooper Industries, Inc.

Page 5

Image 5
Contents Ratings ApplicationDetail indication logic is given below EVLA12Install ELPS502 System or ELPS50 Power Supply InstallationAttach and Adjust EVLA12 Lighting Fixtures ELPS50 Power Supply= Batt + = L + Conduit Connection and Wiring= 220/240 = L Remote Mounting EVLA12 Emergency Light Only Periodic TestingComplete Installation Fixture Lamp Replacement Battery ReplacementExit Sign Lamp Replacement Pilot Light Lamp ReplacementMaintenance Replacement Circuit Board & Battery KITBreather and Drain = GRD = 220/240Time Delay Feature Connect AC Power and Test SystemTroubleshooting Guide Wire Sizing for Remote InstallationElps EVI Emergency Lighting Fixture Exit Sign Nfpa 101 2003 RequirementsElps EVA GB Emergency Lighting Fixture GB Group B Exit Sign 30 SECAvertissement ClassificationDEL éteinte Charge complèteFixation et réglage du ou des luminaires EVLA12 RemarqueMise EN Garde Schéma de câblage Raccord de conduite et câblageEssai Régulier Achèvement de linstallationRemplacement DE Lampoule DE Lenseigne DE Sortie Remplacement DE LA PileRemplacement DE Lampoule DU Luminaire Remplacement DE Lampoule DE LA Lampe TémoinReniflard ET Purge EntretienLA Trousse ELPS-K50 Comprend DEL illuminé sans clignotements Charge complèteRebrancher Lalimentation Secteur ET Tester LE Système Calibre de fil pour une installation à distanceCaractéristique DE Délai Dinterruption Guide DE DépannageSpécifications DE LA Nfpa 101 Fiche DentretienEspecificaciones AplicaciónImportante PrecauciónFije y ajuste el o los Accesorios de Iluminación EVLA12 InstalaciónNota = Batt + Conexión de conductos y cableado= L + = Batt Vea la nota de Precaución más abajoMontaje remoto de la Luz de Emergencia EVLA12 únicamente Pruebas PeriódicasComplete la instalación Reemplazo DE Lalámparade Laseñal DE Salida Reemplazo DE LA BateríaReemplazo DE LA Lámpara DEL Accesorio Reemplazo DE LA Lámpara PilotoReemplazodelaplacadecircuitosyelkitdebatería Configure el interruptor de desconexión designado en OFFMantenimiento Respiradero Y DrenajeConecte LA Energía AC Y Pruebe EL Sistema Guía DE Solución DE ProblemasFunción DE Temporización TablaFecha 30 1-1/2 Requisitos Nfpa 101Señal DE Salida GB Grupo B