Environmental specifications

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Conductive dust

NOTE: Applies to data center and non-data center environments.

Corrosive dust

NOTE: Applies to data center and non-data center environments.

Gaseous contamination

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less than 60% relative humidity.

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Copper coupon corrosion rate

<300 Å/month per Class G1 as defined by ANSI/

 

ISA71.04-1985.

Silver coupon corrosion rate

<200 Å/month as defined by AHSRAE TC9.9.

Expanded operating temperature

NOTE: When operating in the expanded temperature range, system performance may be impacted.

NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.

Continuous operation

5°C to 40°C at 5% to 85% RH with 29°C dew point.

 

NOTE: Outside the standard operating

 

temperature (10°C to 35°C), the system can

 

operate continuously down to 5°C or as high

 

as 40°C.

 

For temperatures between 35°C and 40°C, de-

 

rate maximum allowable temperature by 1°C per

 

175 m above 950 m (1°F per 319 ft).

< 1% of annual operating hours

–5°C to 45°C at 5% to 90% RH with 29°C dew

 

point.

 

NOTE: Outside the standard operating

 

temperature (10°C to 35°C), the system can

 

operate down to –5°C or up to 45°C for a

 

maximum of 1% of its annual operating hours.

110

Image 110
Contents Dell PowerEdge FC630 Page Contents Installing and removing sled components Troubleshooting your system Technical specifications 107 Getting help 112 Using System Diagnostics 102Jumpers and connectors 104 Front-panel features and indicators About your systemUsing USB diskette or USB DVD/CD drives Hard-drive/SSD indicator patternsIDRAC Direct LED indicator codes Hard-drive/SSD indicatorsIDRAC Direct LED indicator Documentation matrix Quick Resource Locator Setting up your system Setting up and configuring the iDRAC IP addressLogging in to iDRAC Installing the operating system Page About System Setup Navigation keysSystem Bios screen Entering System SetupSystem Setup Main Menu System Information screen System Memory screenProcessor Settings screen ATSSata Settings screen Post Page Boot Settings screen Network Settings screenIntegrated Devices screen Serial Communication screen System Profile Settings screen C1ESystem Security Settings screen Miscellaneous Settings screen Secure Boot Custom Policy Settings screenPage Entering Boot Manager About Boot ManagerAbout Dell Lifecycle Controller Changing the boot order Boot Manager main menuChoosing the system boot mode Assigning a system and/or setup passwordUsing your system password to secure your system Embedded systems management Operating with a setup password enabledIDRAC Settings utility Entering the iDRAC Settings utility Before working inside your system Safety instructionsRecommended tools After working inside your systemRemoving and installing a sled Removing the sledO connector cover Installing the sled Removing and installing the sledInside the sled NDCCooling shroud Removing the cooling shroudRemoving a processor/DIMM blank Installing the cooling shroudProcessor/DIMM blank Installing a processor/DIMM blank Removing and installing a processor/DIMM blankSystem memory LrdimmProcessor General memory-module installation guidelines Mode-specific guidelines Advanced ECC LockstepSample memory configurations Memory configurations two processors Removing memory modules Installing memory modules Removing the memory modulePCIe mezzanine card Removing a PCIe mezzanine cardRemoving and installing a PCIe mezzanine card Replacing an SD card Installing a PCIe mezzanine cardIdsdm card optional Ensure that you read the Safety instructions Internal USB key Replacing an SD cardReplacing the internal USB key Removing and installing the Idsdm card Removing the Idsdm cardInstalling the Idsdm card RSPI card optional Removing the rSPI cardReplacing the SD vFlash card Installing the rSPI cardSD vFlash card Network Daughter Card Removing the Network Daughter CardInstall the NDC. See Installing the Network Daughter Card Installing the Network Daughter Card ProcessorsRemoving a processor Installing and removing a heat sink Processor shield opening and closing lever sequence Installing a processor Installing and removing a processorPage Applying thermal grease on the top of the processor Hard-drive/SSD bay numbering Hard drive/SSD installation guidelinesHard drives/SSDs Removing and installing a hard drive/SSD Removing a hard drive/SSDInstalling a hard drive/SSD Removing a hard-drive/SSD blankHard-drive/SSD blank Release latch Configuring the boot drive Installing a hard-drive/SSD blankShutdown procedure for servicing a hard drive/SSD Hard drive/SSD Removing a 1.8 inch SSD from a 1.8 inch SSD carrier Installing a 1.8 inch SSD in a 1.8 inch SSD carrier Removing the hard-drive/SSD cageInstalling the hard-drive/SSD cage Removing and installing a hard-drive/SSD cageHard-drive backplane Removing the hard-drive/SSD backplaneRemoving and installing the hard-drive/SSD backplane Installing the hard-drive/SSD backplane Perc H730P slim card Removing a Perc H730P slim cardInstalling a Perc H730P slim card Removing and installing a Perc H730P slim cardStorage controller card Removing the PCIe extender/storage controller cardPage Installing the PCIe extender/storage controller card Nvram backup battery Replacing the Nvram backup batteryReplacing the Nvram backup battery System board Removing the system boardPage Hex nut screw System board Screw Installing the system board Restoring the Service Tag using Easy Restore Installing the Trusted Platform Module Trusted Platform ModuleRe-enabling the TPM for BitLocker users Re-enabling the TPM for TXT usersTroubleshooting your system Troubleshooting hard drives Troubleshooting USB devicesTroubleshooting Solid State Drives Troubleshooting an internal SD card Troubleshooting processorsTroubleshooting the system board Troubleshooting the Nvram backup batteryAlert messages Diagnostic messagesSystem messages Running the Embedded System Diagnostics Dell Embedded System DiagnosticsWhen to use the Embedded System Diagnostics Running Embedded System Diagnostics from an external media System diagnostics controlsJumpers and connectors System board jumper settingsSystem board connectors CPU1Disabling a forgotten password Technical specifications USB Per ISO 14644-1 with a 95% upper confidence 110 Page Documentation feedback Locating your system Service TagContacting Dell 113