StreamLight VF-PS1 instruction manual Fwd, About changing parameter settings

Page 10

E6581429

QLCD panel

This section explains the features of windows available, using the top window of Status Monitor Mode as an example.

1

(1)

Status Monitor Mode

Real-time information

 

Rotative direction

FWD

 

 

Frequency reference

60.0Hz

 

Output current

90%

 

 

Input voltage

99%

 

 

Output voltage

99%

 

Top

Prm

(2)

(3)

(4)

(5)

 

 

(6)

(1): Displays the mode currently selected.

(2): Displays the operating status of the inverter with a graphical symbol.

 

(Rotating)

: In operation

 

 

 

: Operation impossible (While the frequency is set at 0Hz, the [RUN] key is pressed.)

 

 

EOFF (blinking)

: Waiting for emergency stop operation

(3): Displays the title or status of the window.

(4): Displays settings both in a menu form and numerically, or a list of various kinds of information.

(5): Displays the function assigned to each function key in an abbreviation or graphical symbol. The abbreviations

and graphical symbols in the window correspond to the [F1] to [F4] keys, respectively starting from the left.

Top

: In this example, pressing the [F1] key displays the Top View Mode window.

 

 

: In this example, pressing the [F2] key displays the previous window.

 

 

 

 

: In this example, pressing the [F3] key displays the next window.

 

 

 

 

Prm

: In this example, pressing the [F4] key displays the Parameter Setting Mode window.

For details, refer to “5. List of function key functions”.

(6)Graphical symbols displayed vary depending on whether there are windows that precede or follow the current window.

: There are windows that precede and/or follow the current window.

: There is no window that precedes or follows the current window.

QAbout changing parameter settings

By default, the inverter is set with parameters to the mode in which it controls the operation of the machine via a terminal board. Moreover, the inverter is set so that the switching between forward run and reverse run cannot be performed using its operation panel.

To operate the inverter using this unit, parameter settings need to be changed, as described below.

Parameter CMOd (Command input mode)

= 1

(Pane/LCD-option)

Parameter FMOd (Frequency input mode 1)

= 4

(Pane/LCD-option)

Parameter Fr (Panel FWD/REV selection)

= 2

(Forward (switchable)),

 

3 (Reverse (switchable))

This change of parameter settings makes it possible to start operation using the [RUN] key, to stop operation using the [STOP/RESET] key, and to switch between forward run and reverse run using the [FWD/REV] key. Furthermore, it allows you to set an operation frequency using the control dial.

Refer to “3.3.1 Setting a panel operation frequency.”

A-4

Image 10
Contents Tosverttm VF-PS1 Page Safety precautions Transportation & installationII. Introduction Contents Page Check the product Contents of the product codeRead first This manual E6581386Structure of the main body Names and functions Outside viewLCD panel STOP/RESET key The drive stops operationOperation panel To 5 F1 to F4 function keysAbout changing parameter settings FWDMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Detaching the cover Front coverCharge lamp Grounding capacitor switching methodVFPS1-4007PLE~4220PLE Case of adopting external braking resistor Optional VFPS1-4300PLE~4900PLEInstallation Installation environment How to installConnection of equipment Standard connection diagram sink logic Standard connectionsStandard connection diagram source logic Main circuit terminals Power supply and motor connectionsDescription of terminals Connection with peripheral equipmentOperations Settings to be made at first power onLanguage Selection window appears Parameter Setup Mode Setting/monitor modesTop View Mode Status Monitor ModePress the control dial Operation in Top View ModeSetting a panel operation frequency Explanation of the top windowUsing an Easy key function Select/confirm the desired language with the control dial Selecting a language to be displayedPress the F2 Lng key Performing jog runThen press the STOP/RESET key again Emergency stop / reset operationPress the STOP/RESET key Press the F4 key to carry out jog runWhen Quick mode is selected Searching and setting parametersSelect/confirm History function using the control dial This window, settings can be changedEx. Select/confirm Command input mode and Base frequency Setting a basic parameterSelect/confirm Basic parameters using the control dial F1 F2 F3Select/confirm Extended parameters using the control dial Setting an extended parameterChange the parameter setting Select/confirm Changed Parameters using the control dial CMOdMonitoring the operation status Items displayed Description Display of detailsSelect/confirm the desired item using the control dial Displaying details of an item monitoredList of function key functions Function key Display Reference PositionPage Measures to satisfy the standards How to cope with the CE standardsMeasures to satisfy the EMC directive Ex. Countermeasure inverter wiring PLE typePDE type RES, PWR, noWiring port plate PLE type PDE type Measurements to be taken to satisfy the UL/CSA standards Conforming to UL TypeSelection of wiring materials and devices Selection of peripheral devicesSelection of wiring equipment Rated current a AC-1Table of parameters PWMPage Specifications Models and their standard specificationsOverleaf LCD Outside dimensions and weight Outside dimensions and massOutline drawing Fig. C Fig. G