7.2Measurements to be taken to satisfy the UL/CSA standards

7.2.1Caution as to peripheral devices

When installing a no-fuse circuit breaker or a fuse box on the primary side of the inverter, use UL-certified one. The UL certification test on this inverter was conducted under the AIC* conditions shown in table below (*: current that flows in the event of a short-circuit in the power supply). Note that AIC currents vary depending on the capacity of the motor used.

 

 

 

 

 

 

AIC and maximum input voltage

 

 

 

 

 

 

 

Applicable motor

AIC

Maximum input voltage

 

 

 

 

 

 

 

 

(kW)

(A)

(V)

 

 

 

 

 

 

 

 

0.4 ~ 37

5,000

480

 

 

 

 

 

 

 

 

45 ~ 90

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIC, Fuse and Wire sizes

 

 

 

 

 

 

Applicable

 

 

 

UL

AIC (A)

 

Input wire size

Output wire size

Grounding

 

 

 

 

 

Fuse class and

of power circuit

of power circuit

wire

 

 

motor

Inverter type form

 

Output current(A)

(Interrupting

 

 

(kW)

 

 

 

*1, *2

capacity)

current (A)

(AWG)

(AWG)

(AWG)

 

 

 

 

 

 

*3

*3

 

*3

 

 

 

 

 

 

 

 

 

 

 

 

0.75

VFPS1-4007PLE/PDE

 

2.1 (CF=8)

AIC 5000A

CC 6Amax.

14

14

 

14

 

 

1.5

VFPS1-4015PLE/PDE

 

3.4 (CF=8)

AIC 5000A

CC 6Amax.

14

14

 

14

 

 

2.2

VFPS1-4022PLE/PDE

 

4.8 (CF=8)

AIC 5000A

CC 12Amax.

14

14

 

14

 

 

3.7

VFPS1-4037PLE/PDE

 

7.6 (CF=8)

AIC 5000A

J 15Amax.

12

12

 

14

 

 

5.5

VFPS1-4055PLE/PDE

 

11.0 (CF=8)

AIC 5000A

J 25Amax.

10

10

 

12

 

 

7.5

VFPS1-4075PLE/PDE

 

14. 0 (CF=8)

AIC 5000A

J 40Amax.

10

10

 

12

 

 

11

VFPS1-4110PLE/PDE

 

21.0 (CF=8)

AIC 5000A

J 40Amax.

8

8

 

10

 

 

15

VFPS1-4150PLE/PDE

 

27.0 (CF=8)

AIC 5000A

J 60Amax.

6

6

 

10

 

 

18.5

VFPS1-4185PLE/PDE

 

34.0 (CF=4)

AIC 5000A

J 70Amax.

6

6

 

10

 

 

22

VFPS1-4220PLE/PDE

 

40.0 (CF=4)

AIC 5000A

J 70Amax.

6

6

 

10

 

 

30

VFPS1-4300PLE/PDE

 

52.0 (CF=4)

AIC 5000A

J 80Amax.

4

4

 

10

 

 

37

VFPS1-4370PLE/PDE

 

65.0 (CF=4)

AIC 5000A

J 90Amax.

3

3

 

8

7

 

45

VFPS1-4450PLE/PDE

 

77.0 (CF=4)

AIC 10000A

J 110Amax.

1

1

 

8

 

55

VFPS1-4550PLE/PDE

 

96.0 (CF=4)

AIC 10000A

J 150Amax.

1/0

1/0

6

 

 

75

VFPS1-4750PLE/PDE

 

124.0 (CF=4)

AIC 10000A

J 175Amax.

3/0

3/0

6

 

 

 

90

VFPS1-4900PCE/PDE

 

156.0 (CF=4)

AIC 10000A

J 225Amax.

250MCM

250MCM

2

*1: UL output current is different from unit rating output current.

*2: The value of the UL rated output current is applicable when the carrier frequency (CF) is less than the value shown in the table.

*3: The cables used must be 75°C copper cables within 40°C ambient temperature.

7.2.2 Conforming to UL Type 12

Drives with UL Type 12 conformity are optional. Contact your nearest Toshiba inverter distributor for them.

G-4

Image 42
Contents Tosverttm VF-PS1 Page Safety precautions Transportation & installationII. Introduction Contents Page Check the product Contents of the product codeRead first This manual E6581386Structure of the main body Names and functions Outside viewLCD panel STOP/RESET key The drive stops operationOperation panel To 5 F1 to F4 function keysAbout changing parameter settings FWDMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Detaching the cover Front coverGrounding capacitor switching method Charge lampVFPS1-4007PLE~4220PLE Case of adopting external braking resistor Optional VFPS1-4300PLE~4900PLEInstallation Installation environment How to installConnection of equipment Standard connection diagram sink logic Standard connectionsStandard connection diagram source logic Main circuit terminals Power supply and motor connectionsDescription of terminals Connection with peripheral equipmentSettings to be made at first power on OperationsLanguage Selection window appears Parameter Setup Mode Setting/monitor modesTop View Mode Status Monitor ModePress the control dial Operation in Top View ModeSetting a panel operation frequency Explanation of the top windowUsing an Easy key function Select/confirm the desired language with the control dial Selecting a language to be displayedPress the F2 Lng key Performing jog runThen press the STOP/RESET key again Emergency stop / reset operationPress the STOP/RESET key Press the F4 key to carry out jog runWhen Quick mode is selected Searching and setting parametersSelect/confirm History function using the control dial This window, settings can be changedEx. Select/confirm Command input mode and Base frequency Setting a basic parameterSelect/confirm Basic parameters using the control dial F1 F2 F3Setting an extended parameter Select/confirm Extended parameters using the control dialChange the parameter setting Select/confirm Changed Parameters using the control dial CMOdMonitoring the operation status Items displayed Description Display of detailsSelect/confirm the desired item using the control dial Displaying details of an item monitoredList of function key functions Function key Display Reference PositionPage How to cope with the CE standards Measures to satisfy the standardsMeasures to satisfy the EMC directive Ex. Countermeasure inverter wiring PLE typePDE type RES, PWR, noWiring port plate PLE type PDE type Measurements to be taken to satisfy the UL/CSA standards Conforming to UL TypeSelection of wiring materials and devices Selection of peripheral devicesSelection of wiring equipment Rated current a AC-1Table of parameters PWMPage Specifications Models and their standard specificationsOverleaf LCD Outside dimensions and mass Outside dimensions and weightOutline drawing Fig. C Fig. G