StreamLight VF-PS1 instruction manual Standard connection diagram source logic

Page 23

E6581429

[Standard connection diagram – source logic]

The figure below shows an example of typical wiring in the main circuit 200V 0.4-45kW/400V 0.75-75kW inverter. This inverter has following three setting/monitor modes.

2

*1: A DC reactor (DCL) is incorporated in the position shown the figure above. External DC reactor cannot be used.

*2: For 30kW to 90kW drives, an additional DC reactor is incorporated in the position shown the figure above.

*3: The noise filter is built in.

*4: External braking resistor (option). Dynamic braking drive circuit (GTR7) is built-in as standard.

*5: To supply a DC power, connect the cables to the PA/+ and PC/- terminals.

*6: If you want to use a DC power supply to operate 30kW or more inverters, be sure to contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.

*7: Refer to Section 2.3.2 of instruction manual E6581386 for each switch functions.

*8: The functions assigned to terminals OUT1, VI/II and RR/S4 can be switched by changing parameter settings.

For details, refer to Section 2.3.2 of instruction manual E6581386.

*9: To supply control power from an external power supply for backing up the control power supplied from the inverter, an optional control power backup device (CPS002Z) is required. In such a case, the backup device is used at the same time with the internal power supply of the inverter.

To back up control power, set the parameter F647 (Control power supply backup option failure monitoring) properly.

For more information, refer to 6.33.22 of instruction manual E6581386.

*10: For PWR connection conforming to safety standards, refer to Section 9.3 of instruction manual E6581386.

B-3

Image 23
Contents Tosverttm VF-PS1 Page Transportation & installation Safety precautionsII. Introduction Contents Page This manual E6581386 Contents of the product codeRead first Check the productNames and functions Outside view Structure of the main bodyTo 5 F1 to F4 function keys STOP/RESET key The drive stops operationOperation panel LCD panelFWD About changing parameter settingsMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Front cover Detaching the coverVFPS1-4007PLE~4220PLE Grounding capacitor switching methodCharge lamp VFPS1-4300PLE~4900PLE Case of adopting external braking resistor OptionalHow to install Installation Installation environmentConnection of equipment Standard connections Standard connection diagram sink logicStandard connection diagram source logic Connection with peripheral equipment Power supply and motor connectionsDescription of terminals Main circuit terminalsLanguage Selection window appears Settings to be made at first power onOperations Status Monitor Mode Setting/monitor modesTop View Mode Parameter Setup ModeExplanation of the top window Operation in Top View ModeSetting a panel operation frequency Press the control dialUsing an Easy key function Performing jog run Selecting a language to be displayedPress the F2 Lng key Select/confirm the desired language with the control dialPress the F4 key to carry out jog run Emergency stop / reset operationPress the STOP/RESET key Then press the STOP/RESET key againThis window, settings can be changed Searching and setting parametersSelect/confirm History function using the control dial When Quick mode is selectedF1 F2 F3 Setting a basic parameterSelect/confirm Basic parameters using the control dial Ex. Select/confirm Command input mode and Base frequencyChange the parameter setting Setting an extended parameterSelect/confirm Extended parameters using the control dial CMOd Select/confirm Changed Parameters using the control dialItems displayed Description Display of details Monitoring the operation statusDisplaying details of an item monitored Select/confirm the desired item using the control dialFunction key Display Reference Position List of function key functionsPage Measures to satisfy the EMC directive How to cope with the CE standardsMeasures to satisfy the standards RES, PWR, no Ex. Countermeasure inverter wiring PLE typePDE typeWiring port plate PLE type PDE type Conforming to UL Type Measurements to be taken to satisfy the UL/CSA standardsSelection of peripheral devices Selection of wiring materials and devicesRated current a AC-1 Selection of wiring equipmentPWM Table of parametersPage Models and their standard specifications SpecificationsOverleaf LCD Outline drawing Outside dimensions and massOutside dimensions and weight Fig. C Fig. G