StreamLight VF-PS1 instruction manual Selection of wiring equipment, Rated current a AC-1

Page 44

E6581429

QSelection of wiring equipment

Applicable motor

Inverter type form

Input current [A]

No-fuse breaker (MCCB)

Magnetic contactor (MC)

(kW)

Rated current [A]

Rated current [A] AC-1

 

 

0.75

VFPS1-4007PLE/PDE

1.8

4

25

1.5

VFPS1-4015PLE/PDE

3.5

6.3

25

2.2

VFPS1-4022PLE/PDE

5

10

25

3.7

VFPS1-4037PLE/PDE

8.8

14

25

5.5

VFPS1-4055PLE/PDE

11.4

25

25

7.5

VFPS1-4075PLE/PDE

15.8

25

25

11

VFPS1-4110PLE/PDE

21.9

30

32

15

VFPS1-4150PLE/PDE

30.5

40

40

18.5

VFPS1-4185PLE/PDE

37.5

60

50

22

VFPS1-4220PLE/PDE

43.6

60

50

30

VFPS1-4300PLE/PDE

56.7

100

80

37

VFPS1-4370PLE/PDE

69.5

100

125

45

VFPS1-4450PLE/PDE

85.1

125

125

55

VFPS1-4550PLE/PDE

104.8

150

125

75

VFPS1-4750PLE/PDE

140.3

200

250

90

VFPS1-4900PLE/PDE

171.8

200

250

(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 400V-50Hz.

(*2): Choose the MCCB according to the power supply capacity.

For comply with UL and CSA standard, use the fuse certified by UL and CSA.

(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for the motor rated current.

(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.

(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of the contact by using 2a-type contacts in parallel connection.

8

H-2

Image 44
Contents Tosverttm VF-PS1 Page Safety precautions Transportation & installationII. Introduction Contents Page Contents of the product code Read firstCheck the product This manual E6581386Structure of the main body Names and functions Outside viewSTOP/RESET key The drive stops operation Operation panelLCD panel To 5 F1 to F4 function keysAbout changing parameter settings FWDMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Detaching the cover Front coverVFPS1-4007PLE~4220PLE Grounding capacitor switching methodCharge lamp Case of adopting external braking resistor Optional VFPS1-4300PLE~4900PLEInstallation Installation environment How to installConnection of equipment Standard connection diagram sink logic Standard connectionsStandard connection diagram source logic Power supply and motor connections Description of terminalsMain circuit terminals Connection with peripheral equipmentLanguage Selection window appears Settings to be made at first power onOperations Setting/monitor modes Top View ModeParameter Setup Mode Status Monitor ModeOperation in Top View Mode Setting a panel operation frequencyPress the control dial Explanation of the top windowUsing an Easy key function Selecting a language to be displayed Press the F2 Lng keySelect/confirm the desired language with the control dial Performing jog runEmergency stop / reset operation Press the STOP/RESET keyThen press the STOP/RESET key again Press the F4 key to carry out jog runSearching and setting parameters Select/confirm History function using the control dialWhen Quick mode is selected This window, settings can be changedSetting a basic parameter Select/confirm Basic parameters using the control dialEx. Select/confirm Command input mode and Base frequency F1 F2 F3Change the parameter setting Setting an extended parameterSelect/confirm Extended parameters using the control dial Select/confirm Changed Parameters using the control dial CMOdMonitoring the operation status Items displayed Description Display of detailsSelect/confirm the desired item using the control dial Displaying details of an item monitoredList of function key functions Function key Display Reference PositionPage Measures to satisfy the EMC directive How to cope with the CE standardsMeasures to satisfy the standards Ex. Countermeasure inverter wiring PLE typePDE type RES, PWR, noWiring port plate PLE type PDE type Measurements to be taken to satisfy the UL/CSA standards Conforming to UL TypeSelection of wiring materials and devices Selection of peripheral devicesSelection of wiring equipment Rated current a AC-1Table of parameters PWMPage Specifications Models and their standard specificationsOverleaf LCD Outline drawing Outside dimensions and massOutside dimensions and weight Fig. C Fig. G