E6581429
QVFPS1-4300PLE~4900PLE
A switch or switches enable to reduce grounding capacitance.
Large Small
*2
Large Small
*2:
⇒For details, refer to main circuit terminal
Q
Q
A switch enables to reduce grounding capacitance.
Large Small
Large Small
To change the capacitance from small to large, push in the button.
(Factory default position)
To change the capacitance
from large to small, pull up1 the button.
To change the capacitance from small to large, slide the switch in direction shown left. (Factory default position)
To change the capacitance from large to small, slide the switch in direction shown left.
1.3.4 In case of adopting external braking resistor (Optional)
To wire for external braking resistor, an attention is needed because PA/+ terminal have a wiring to the internal DC reactor. Refer to followings when you wire for external braking resistor.
Q0.75~22kW
With reference of the figure right, make the each solderless terminal in back to back and fasten them with the screw.
PA/+ terminal screw
Wiring to the internal DC reactor
Wiring to the external braking resistor
Q30~90kW
Fasten with the screw both of copper bar connected to the PA/+ terminal and the stripped cable for external braking resistor.