StreamLight VF-PS1 Operation in Top View Mode, Setting a panel operation frequency

Page 27
Display of commands Display of
executedoperating status

E6581429

3.3 Operation in Top View Mode

When the inverter is powered on, it enters this mode first, which allows you to monitor the operating status, set an operation frequency, use EASY key, and switch between languages.

When Panel Jog Run is selected, a jog run frequency also can be specified in this mode.

QExplanation of the top window

• Display of commands executed:

“FWD” or “REV” is displayed to indicate the direction of rotation. The operation frequency is displayed in the form of “††. †Hz”.

• Display of operating status:

“RUN” is displayed during operation. “STOP” is displayed during a stop.

“Trip” is displayed in the event of tripping.

• Display of output frequency:

The operation frequency is displayed in the form of “††. †Hz”.

• Display of alarm/trip:

In case of alarm or trip, Its code is displayed.

• Display of alarm/trip information:

In case of alarm or trip, Its information is displayed.

Functions of function keys

F1 : Switches between Quick mode and Standard Setting mode.

F2 : Goes to the Language selection window.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top

 

View Mode

 

 

 

 

 

 

 

 

 

 

 

FWD

60.0 Hz

 

 

 

 

 

 

RUN

 

 

 

 

 

 

 

 

60.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overheat alarm

 

 

 

 

 

 

 

 

 

 

 

 

Quick

 

 

Lng

 

 

---

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1

 

 

F2

 

 

 

 

 

 

 

 

 

Display of output frequency Display of alarm/trip

Display of alarm/trip message

3.3.1 Setting a panel operation frequency

Only when Frequency input mode selection 1 (parameter “FMOd”) is set at “4”, panel operation frequency setting is activated.

1. Press the control dial.

The panel frequency window appears.

The current operation frequency setting is displayed at the center of the window.

The current output frequency is displayed in the upper right section of the window.

The minimum allowable frequency (min) and the maximum allowable frequency (max) are displayed at the bottom of the window.

Basic Parameters

FC

Panel frequency

Output frequency

 

0.0Hz

 

0.0Hz

 

min=0.0

 

 

max=60.0

 

 

 

 

×1000

×100

×10

×1

Functions of function keys

F1

F2

F3

F4

The functions keys allow you to select the position or decimal place of each figure (operation frequency) you want to increment or decrement with the control dial.

F1 : Selects the position of 1000 times of minimum setting unit.

F2 : Selects the position of 100 times of minimum setting unit.

F3 : Selects the position of 10 times of minimum setting unit.

F4 : Selects the position of minimum setting unit (In this case, 0.1).

C-3

Image 27
Contents Tosverttm VF-PS1 Page Transportation & installation Safety precautionsII. Introduction Contents Page This manual E6581386 Contents of the product codeRead first Check the productNames and functions Outside view Structure of the main bodyTo 5 F1 to F4 function keys STOP/RESET key The drive stops operationOperation panel LCD panelFWD About changing parameter settingsMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Front cover Detaching the coverGrounding capacitor switching method Charge lampVFPS1-4007PLE~4220PLE VFPS1-4300PLE~4900PLE Case of adopting external braking resistor OptionalHow to install Installation Installation environmentConnection of equipment Standard connections Standard connection diagram sink logicStandard connection diagram source logic Connection with peripheral equipment Power supply and motor connectionsDescription of terminals Main circuit terminalsSettings to be made at first power on OperationsLanguage Selection window appears Status Monitor Mode Setting/monitor modesTop View Mode Parameter Setup ModeExplanation of the top window Operation in Top View ModeSetting a panel operation frequency Press the control dialUsing an Easy key function Performing jog run Selecting a language to be displayedPress the F2 Lng key Select/confirm the desired language with the control dialPress the F4 key to carry out jog run Emergency stop / reset operationPress the STOP/RESET key Then press the STOP/RESET key againThis window, settings can be changed Searching and setting parametersSelect/confirm History function using the control dial When Quick mode is selectedF1 F2 F3 Setting a basic parameterSelect/confirm Basic parameters using the control dial Ex. Select/confirm Command input mode and Base frequencySetting an extended parameter Select/confirm Extended parameters using the control dialChange the parameter setting CMOd Select/confirm Changed Parameters using the control dialItems displayed Description Display of details Monitoring the operation statusDisplaying details of an item monitored Select/confirm the desired item using the control dialFunction key Display Reference Position List of function key functionsPage How to cope with the CE standards Measures to satisfy the standardsMeasures to satisfy the EMC directive RES, PWR, no Ex. Countermeasure inverter wiring PLE typePDE typeWiring port plate PLE type PDE type Conforming to UL Type Measurements to be taken to satisfy the UL/CSA standardsSelection of peripheral devices Selection of wiring materials and devicesRated current a AC-1 Selection of wiring equipmentPWM Table of parametersPage Models and their standard specifications SpecificationsOverleaf LCD Outside dimensions and mass Outside dimensions and weightOutline drawing Fig. C Fig. G