1.4 Notes on the application

1.4.1 Installation

QInstallation environment

Operate in areas where ambient temperature ranges from –10°C to 50°C.

Where ambient temperature will rise above 40°C, derating of rated current is needed.

 

• Install the inverter in a well-ventilated place and mount it

5cm or more

1

on a flat metal plate in portrait operation.

 

 

• Leave a space of 10cm or more on the upper and lower

 

sides of the inverter, and a space of 5cm or more on each

 

 

side.

 

This inverter have a structure with IP54 conformity.

IP54 is a structure that protects the contents from dust and harmful effects of water that drops from every direction.

10cm or more

VF-PS1

5cm or more

 

10cm or more

QHow to install

QDerating curves

Derating curves in E6581386 manual are only for standard models. For totally enclosed box type, refer to following derating curves.

0.75~2.2, 30kW

3.7, 5.5kW

7.5, 11kW

15~22, 37~90kW

A-14

Image 20
Contents Tosverttm VF-PS1 Page Safety precautions Transportation & installationII. Introduction Contents Page Contents of the product code Read firstCheck the product This manual E6581386Structure of the main body Names and functions Outside viewSTOP/RESET key The drive stops operation Operation panelLCD panel To 5 F1 to F4 function keysAbout changing parameter settings FWDMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Detaching the cover Front coverVFPS1-4007PLE~4220PLE Grounding capacitor switching methodCharge lamp Case of adopting external braking resistor Optional VFPS1-4300PLE~4900PLEInstallation Installation environment How to installConnection of equipment Standard connection diagram sink logic Standard connectionsStandard connection diagram source logic Power supply and motor connections Description of terminalsMain circuit terminals Connection with peripheral equipmentLanguage Selection window appears Settings to be made at first power onOperations Setting/monitor modes Top View ModeParameter Setup Mode Status Monitor ModeOperation in Top View Mode Setting a panel operation frequencyPress the control dial Explanation of the top windowUsing an Easy key function Selecting a language to be displayed Press the F2 Lng keySelect/confirm the desired language with the control dial Performing jog runEmergency stop / reset operation Press the STOP/RESET keyThen press the STOP/RESET key again Press the F4 key to carry out jog runSearching and setting parameters Select/confirm History function using the control dialWhen Quick mode is selected This window, settings can be changedSetting a basic parameter Select/confirm Basic parameters using the control dialEx. Select/confirm Command input mode and Base frequency F1 F2 F3Change the parameter setting Setting an extended parameterSelect/confirm Extended parameters using the control dial Select/confirm Changed Parameters using the control dial CMOdMonitoring the operation status Items displayed Description Display of detailsSelect/confirm the desired item using the control dial Displaying details of an item monitoredList of function key functions Function key Display Reference PositionPage Measures to satisfy the EMC directive How to cope with the CE standardsMeasures to satisfy the standards Ex. Countermeasure inverter wiring PLE typePDE type RES, PWR, noWiring port plate PLE type PDE type Measurements to be taken to satisfy the UL/CSA standards Conforming to UL TypeSelection of wiring materials and devices Selection of peripheral devicesSelection of wiring equipment Rated current a AC-1Table of parameters PWMPage Specifications Models and their standard specificationsOverleaf LCD Outline drawing Outside dimensions and massOutside dimensions and weight Fig. C Fig. G