StreamLight VF-PS1 Grounding capacitor switching method, Charge lamp, VFPS1-4007PLE~4220PLE

Page 18

E6581429

QCharge lamp

Charge lamp is inside the unit front cover open. Never remove the front cover while power is on or within 15 minutes after power off, nor turn on the power while the front cover is open. They can result in electric shock. Location of charge lamp depends on type form.

VFPS1-4007PLE~4220PLE VFPS1-4007PDE~4220PDE

VFPS1-4300PLE~4900PLE VFPS1-4300PDE~4900PDE

1

Charge lamp

Charge lamp

1.3.3 Grounding capacitor switching method

The inverter is grounded through a capacitor. The leakage current from the inverter can be reduced using the switching switch on the main circuit terminal board. This switching device is used to detach the capacitor from the grounding circuit or to reduce its capacitance.

Some models have capacitors that can be detached completely, while others have capacitors whose capacitances can be reduced.

VFPS1-4007PDE to 4220PDE don’t have this switch.

Note 1: Please note that, without the capacitor, the inverter does not comply with the EMC directive.

With default setting, PLE type drives comply with EN55011 class A, and PDE type drives comply with EN55011 class B. For detailed information, refer to 7.1.1.

Note 2: When attaching or detaching the capacitor, be sure to turn off power.

QVFPS1-4007PLE~4220PLE

Danger

If you are using one of VFPS1-4007PLE~4055PLE inverter, or one of 4075PLE~4220PLE inverter with the cable between inverter to the motor which length is 100m or more, in case of detaching the grounding capacitor, be sure to set the carrier frequency (CF) at

Prohibited 4kHz or less. If the carrier frequency is set above 4kHz, internal parts of the inverter may overheat and be damaged.

A switch enables to detach the grounding capacitor. However, if you are using one of VFPS1-4007PLE~4055PLE inverter, or one of 4075PLE~4220PLE inverter with the cable between inverter to the motor which length is 100m or more, detaching the grounding capacitor must be followed with setting the carrier frequency (CF) at 4kHz or less. Be sure to read the above precaution.

To connect and ground the capacitor, push in the

*1 button.

*1

Pull up this part to detach the capacitor to prevent it from being grounded.

*1: For 4007PLE~4055PLE inverter, the switch is fixed with a label saying

“CF/SFr 4kHz”. If such a label is affixed to your inverter, you should set the carrier frequency (CF) at 4kHz or less according to the instructions when switching.

A-12

Image 18
Contents Tosverttm VF-PS1 Page Safety precautions Transportation & installationII. Introduction Contents Page Check the product Contents of the product codeRead first This manual E6581386Structure of the main body Names and functions Outside viewLCD panel STOP/RESET key The drive stops operationOperation panel To 5 F1 to F4 function keysAbout changing parameter settings FWDMain circuit terminal VFPS1-4037PDE, 4055PDE VFPS1-4150PLE PO PA/+ PE PO PA/+ PB PC/- PE PA/+ Detaching the cover Front coverGrounding capacitor switching method Charge lampVFPS1-4007PLE~4220PLE Case of adopting external braking resistor Optional VFPS1-4300PLE~4900PLEInstallation Installation environment How to installConnection of equipment Standard connection diagram sink logic Standard connectionsStandard connection diagram source logic Main circuit terminals Power supply and motor connectionsDescription of terminals Connection with peripheral equipmentSettings to be made at first power on OperationsLanguage Selection window appears Parameter Setup Mode Setting/monitor modesTop View Mode Status Monitor ModePress the control dial Operation in Top View ModeSetting a panel operation frequency Explanation of the top windowUsing an Easy key function Select/confirm the desired language with the control dial Selecting a language to be displayedPress the F2 Lng key Performing jog runThen press the STOP/RESET key again Emergency stop / reset operationPress the STOP/RESET key Press the F4 key to carry out jog runWhen Quick mode is selected Searching and setting parametersSelect/confirm History function using the control dial This window, settings can be changedEx. Select/confirm Command input mode and Base frequency Setting a basic parameterSelect/confirm Basic parameters using the control dial F1 F2 F3Setting an extended parameter Select/confirm Extended parameters using the control dialChange the parameter setting Select/confirm Changed Parameters using the control dial CMOdMonitoring the operation status Items displayed Description Display of detailsSelect/confirm the desired item using the control dial Displaying details of an item monitoredList of function key functions Function key Display Reference PositionPage How to cope with the CE standards Measures to satisfy the standardsMeasures to satisfy the EMC directive Ex. Countermeasure inverter wiring PLE typePDE type RES, PWR, noWiring port plate PLE type PDE type Measurements to be taken to satisfy the UL/CSA standards Conforming to UL TypeSelection of wiring materials and devices Selection of peripheral devicesSelection of wiring equipment Rated current a AC-1Table of parameters PWMPage Specifications Models and their standard specificationsOverleaf LCD Outside dimensions and mass Outside dimensions and weightOutline drawing Fig. C Fig. G