INSTALLATION | ||
|
|
|
REMOTE CONTROL
The VANTAGE® 575 CUMMINS is equipped with a 6- pin and a
When in TOUCH START TIG mode and when a Amptrol is connected to the
In the
The
WARNING
NOTE: When a wire feeder with a built in welding voltage control is connected to the
AUXILIARY POWER RECEPTACLES
The auxiliary power capacity of the VANTAGE® 575 CUMMINS is 20kVA of 50Hz three phase power pro- tected by an RCD (Residual Current Device) and a 3 phase 32 amp circuit breaker. The auxiliary power capacity in watts equivalent to
This model has:
1 x 3 phase and neutral Residual Current Device (RCD) protection (30mA)
1 x 3 phase 32 amp Circuit Breaker
1 x 3 phase 415 volt 32 amp
2 x 1 phase 15 amp Circuit Breakers
2 x 1 phase 240 volt 15 amp per outlet
Note: The
The auxiliary power receptacles should only be used with three or four wire earthed type plugs or approved double insulated tools. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.
STANDBY POWER CONNECTIONS
The VANTAGE® 575 CUMMINS is suitable for tempo- rary, standby or emergency power using the engine manufacturer’s recommended maintenance schedule.
The VANTAGE® 575 CUMMINS can be permanently installed as a standby power unit for 415/240 volt (50 Hz). Connections must be made by a licensed electri- cian who can determine how the 415/240 VAC power can be adapted to the particular installation and com- ply with all applicable electrical codes. The following information can be used as a guide by the electrician for most applications.
1.Install an isolation switch between the power com- pany meter and the premises disconnect.(The VANTAGE® 575 CUMMINS and the power compa- ny supplies must not be connected together).
Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.
2.Take necessary steps to assure load is limited to the capacity of the VANTAGE® 575 CUMMINS by installing a 32 amp, 415 VAC three pole circuit breaker. Loading above the rated output will reduce output voltage below the allowable
3.Install a 32 amp 3 phase plug to the
4.Plug this cable into the 3 phase receptacle on the VANTAGE® 575 CUMMINS case front.
VANTAGE® 575 CUMMINS