Lincoln 500 manual Figure A.2 Connection of the Vantage to Premises Wiring

Page 15

A-7

INSTALLATION

A-7

2.Take necessary steps to assure load is limited to the capacity of the Vantage by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amps. Loading above the rated output will reduce output voltage below the allowable -10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the Vantage engine.

3.Install a 50 amp 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit.)

4.Plug this cable into the 50 Amp 120/240 Volt receptacle on the Vantage case front.

Figure A.2 Connection of the Vantage to Premises Wiring

240Volt

60 Hz.

3-Wire

Service

240 VOLT

POWER

120 VOLT

COMPANY

120 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

DOUBLE POLE DOUBLE THROW

SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

 

 

50AMP

 

 

240 VOLT

 

 

DOUBLE

50 AMP, 120/240

 

POLE

 

CIRCUIT

VOLT PLUG

240 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

N

LOAD

PREMISES

DISCONNECT AND

SERVICE

GROUNDOVERCURRENT

PROTECTION

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

Vantage 500 CUMMINS

Image 15 Contents
Vantage 500 Cummins California Proposition 65 Warnings SafetyElectric Shock can kill Welding Sparks can cause fire or explosion Précautions DE Sûreté Thank You Table of Contents Vii Input Diesel Engine InstallationStacking Safety PrecautionsLocation / Ventilation StoringTowing High Temperature OperationLifting High Altitude OperationFuel USE Diesel Fuel only PRE-OPERATION Engine ServiceBattery Connection OIL Engine CoolantWelding Terminals Output Remote ControlAuxiliary Power Receptacles Standby Power ConnectionsFigure A.2 Connection of the Vantage to Premises Wiring Connection of LN-15 to the Vantage Connection of Lincoln Electric Wire FeedersConnection of AN LN-23P Wire Feeder to the Vantage Connection of LN-7, LN-8 or LN-742 to the VantageConnection of Prince XL Spool GUN to the Vantage Connection of the LN-25 to the VantageSafety Instructions OperationGeneral Description Controls and Settings Engine Protection Battery Charging LightIdler Switch OIL Pressure GaugeAuxiliary Power Controls Engine Operation Starting the EngineStopping the Engine BREAK-IN Period Engine BREAK-INWelder Operation For Tungsten Electrodes Vantage Settings When Using the K930-2 TIG ModuleAuxiliary Power Operation Operation Accessories Optional Field Installed AccessoriesK767-2 Four Wheeled Steerable Yard Trailer Maintenance Routine and Periodic MaintenanceEngine Maintenance Battery Handling Fuel FiltersCooling System Welder / Generator Maintenance HOW to USE Troubleshooting Guide TroubleshootingPossible Areas Recommended Misadjustments Course of ActionPossible Areas Function ProblemsProblems Possible Areas Vangage 500 Cummins Wiring Diagram DiagramsConnection Diagram DIAGRAMSF-2Diagram Commander / K867 / K775 / LN-7 Connection DiagramDiagrams Diagrams Commander / K867 / LN-8 Connection Diagram Diagrams Diagrams Connection Engine Welders /LN-8 Connection DiagramDiagrams Diagrams Diagrams Diagrams M18962-3 Dimension PrintPrecaucion l Aviso DE