Freedom Inverter/Charger Configuration

Setting Battery Types on the Main Unit

You can attach different types of lead-acid batteries to the Freedom HF. Before installing batteries make sure that you configure the unit to optimize the charging process.

The settings can be changed by adjusting the dip switches found on the main unit behind the display panel.

Battery

Dip Switch

Bulk/

Float

Type

Setting

Absorption

 

 

Switch 1Switch 2

 

 

Fixed

OFFOFF

13.5

13.5

 

 

 

 

Flooded

OFFON (default)

14.4

13.5

 

 

 

 

GEL

ONOFF

14.2

13.8

 

 

 

 

AGM

ONON

14.3

13.4

 

 

 

 

To adjust the battery type setting:

By default the battery type is set to Flooded (OFFON).

1.Detach the Display Panel to expose the Dip Switches.

2.Use the tip of your fingernail or a small screw driver with a flat tip to adjust the switches.

OFF

ON

Switch 1 Switch 2

Figure 2 Dip Switches (Default Settings Shown)

975-0390-01-01

9

Image 23
Contents Freedom HF Inverter/Chargers Page Product Numbers Exclusion for DocumentationDocument Part Number Date and RevisionScope About This GuidePurpose Conventions UsedRelated Information Electrical Shock Hazard Important Safety InstructionsFire and Burn Hazard Precautions When Working With Batteries Exposure to Chemicals and Gases Hazard Regulatory Precautions for Using Rechargeable AppliancesKKK Information to the User FCC Information to the UserPage Contents Page Materials List IntroductionKey Features Low Mid High ModelFront Panel Freedom HF 1000, 1055, 1500 FeaturesDefault Setting Your Setting Feature DescriptionFront Panel Freedom HF 1055 EMS,1800 EMS Front Panel Freedom HF 1800 TSerial number of your unit Freedom HF 1055 EMS,1800 EMS Display Panel All Models Remote and Power Module PanelSide Panel All Models Setting Absorption Switch 1Switch Freedom Inverter/Charger ConfigurationSetting Battery Types on the Main Unit Battery Dip Switch Bulk FloatViewing Inverter/Charger Information Screen Adjusting Feature SettingsTo change the charger’s charging current setting To change the inverter mode setting To adjust the low battery shutdown setting Display Panel Operation Freedom Inverter/Charger OperationFreedom Inverter/Charger Operation Inverter Mode Setting is on Standby Operating in Shore Power ModeOperating in Inverter Mode Energy Saver 25-hour Automatic Shut Offa Inverter Mode Setting is OFFLED Status LED During Inverter ModeOperating Several Loads at Once Checking Battery StatusChecking Output Power Turning the Audible Alarm on or OFFTransitioning from Inverter Mode to Shore Power Transitioning from Shore Power to Inverter ModeInput Voltage Power OutputOperating Limits Operating Voltage Range Comment Condition Freedom HF Only High Surge Loads Over-temperature ConditionsInverter Loads Overload ConditionsEquipment Damage Trouble LoadsVoltage Battery ChargingBattery Charging Flooded 14.4 13.5 Batteries Routine MaintenanceFreedom HF Unit Inverter Overload Operation Invert Power Derating vs. Ambient Temperature Invert Power Derating vs. Ambient Temperature Electrical Shock and Energy Hazard TroubleshootingTelevision Reception Common ProblemsBuzz in Audio Equipment  Error Code Condition Mode Action For error codes  to  Problem Possible Cause Solution Troubleshooting ReferenceAC shore power is not available or out Inverter was probably damaged due to the reverse Problem Possible Cause Solution Long Transfer Times Inverter ApplicationsResistive Loads Motor LoadsWatt models 1800-watt models SpecificationsDC Input AC Input Page Page Schneider Electric Solar Inverters USA Inc