Warning Messages

 

Table 7 Error Codes Displayed on the Display Panel Screen

 

 

 

 

 

 

 

Error Code

Condition

Mode

Action

 

 

 

 

 

 



Battery is bad or external DC

AC shore power

• Check the battery bank.

 

 

load is connected to the battery.

 

NOTE: The battery voltage did not rise above 5 volts DC after 1

 

 

 

 

minute or 10 volts DC after 15 minutes.

 

 

 

 

• Check that the external DC load current consumption is below the

 

 

 

 

charging current setting.

 

 

 

 

• Disconnect the DC load or increase the charger current setting.

 

 

 

 

 

 

For error code :

the display screen and the alarm will turn off after 30 secondsa

after a five-minute shutdown delayb, the unit will immediately stop inverting

For error codes  to :

the unit will stop inverting

For error codes  and :

the unit will stop charging, but

the error code will still show on the display screen and the alarm will remain on, and

AC power will continue to pass through to the AC outlets

a.Available in all models except Freedom HF 1500 and 1800 T. See page 22. b.Available only for the Freedom HF 1500 and 1800 T models. See page 23.

For error code 

the unit will stop charging and shut down, and

the error code will show on the display screen briefly, and

AC power will not pass through to the AC outlets

To reset error codes  to :

1.Remove the AC input.

2.Turn the unit OFF and then turn ON again using the Inverter Power button on the display panel.

975-0390-01-01

37

Image 51
Contents Freedom HF Inverter/Chargers Page Product Numbers Exclusion for DocumentationDocument Part Number Date and RevisionScope About This GuidePurpose Conventions UsedRelated Information Electrical Shock Hazard Important Safety InstructionsFire and Burn Hazard Precautions When Working With Batteries Exposure to Chemicals and Gases Hazard Regulatory Precautions for Using Rechargeable AppliancesKKK Information to the User FCC Information to the UserPage Contents Page Materials List IntroductionKey Features Low Mid High ModelFront Panel Freedom HF 1000, 1055, 1500 FeaturesDefault Setting Your Setting Feature DescriptionFront Panel Freedom HF 1055 EMS,1800 EMS Front Panel Freedom HF 1800 TSerial number of your unit Freedom HF 1055 EMS,1800 EMS Display Panel All Models Remote and Power Module PanelSide Panel All Models Setting Absorption Switch 1Switch Freedom Inverter/Charger ConfigurationSetting Battery Types on the Main Unit Battery Dip Switch Bulk FloatViewing Inverter/Charger Information Screen Adjusting Feature SettingsTo change the charger’s charging current setting To change the inverter mode setting To adjust the low battery shutdown setting Display Panel Operation Freedom Inverter/Charger OperationFreedom Inverter/Charger Operation Operating in Shore Power Mode Operating in Inverter ModeInverter Mode Setting is on Standby Energy Saver 25-hour Automatic Shut Offa Inverter Mode Setting is OFFLED Status LED During Inverter ModeOperating Several Loads at Once Checking Battery StatusChecking Output Power Turning the Audible Alarm on or OFFTransitioning from Inverter Mode to Shore Power Transitioning from Shore Power to Inverter ModePower Output Operating LimitsInput Voltage Operating Voltage Range Comment Condition Freedom HF Only High Surge Loads Over-temperature ConditionsInverter Loads Overload ConditionsEquipment Damage Trouble LoadsVoltage Battery ChargingBattery Charging Flooded 14.4 13.5 Routine Maintenance Freedom HF UnitBatteries Inverter Overload Operation Invert Power Derating vs. Ambient Temperature Invert Power Derating vs. Ambient Temperature Electrical Shock and Energy Hazard TroubleshootingCommon Problems Buzz in Audio EquipmentTelevision Reception  Error Code Condition Mode Action For error codes  to  Problem Possible Cause Solution Troubleshooting ReferenceAC shore power is not available or out Inverter was probably damaged due to the reverse Problem Possible Cause Solution Long Transfer Times Inverter ApplicationsResistive Loads Motor LoadsWatt models 1800-watt models SpecificationsDC Input AC Input Page Page Schneider Electric Solar Inverters USA Inc