Xantrex Technology 806-1544, 806-1840, 806-1055-02, 806-1054-01 manual Flooded 14.4 13.5

Page 42

Freedom HF InvChg Owners Guide.book Page 28 Tuesday, April 29, 2014 12:10 PM

Battery Charging

Table 6 illustrates the battery charging voltage and current settings for the Freedom HF 1055 models.

Table 6 Battery Charging Voltage and Current Settings

 

 

 

 

Absorption to

 

Bulk/

 

Charge

Float

Battery

Absorption

Float

Current

transition

Type

(Volts)

(Volts)

(Amps)

(Amps)

 

 

 

 

 

Flooded

14.4

13.5

5, 15

2

 

 

 

35, 55

5

GEL

14.2

13.8

5, 15

2

 

 

 

35, 55

5

AGM

14.3

13.4

5, 15

2

 

 

 

35, 55

5

Fixed

13.5

13.5

5, 15

2

 

 

 

35, 55

5

 

 

 

 

 

28

Freedom HF Owner’s Guide

Image 42
Contents Freedom HF Inverter/Chargers Page Date and Revision Exclusion for DocumentationDocument Part Number Product NumbersConventions Used About This GuidePurpose ScopeRelated Information Important Safety Instructions Electrical Shock HazardFire and Burn Hazard Precautions When Working With Batteries Exposure to Chemicals and Gases Hazard Precautions for Using Rechargeable Appliances RegulatoryFCC Information to the User KKK Information to the UserPage Contents Page Introduction Materials ListKey Features Model Low Mid HighFeature Description FeaturesDefault Setting Your Setting Front Panel Freedom HF 1000, 1055, 1500Front Panel Freedom HF 1800 T Front Panel Freedom HF 1055 EMS,1800 EMSSerial number of your unit Display Panel All Models Remote and Power Module Panel Freedom HF 1055 EMS,1800 EMSSide Panel All Models Battery Dip Switch Bulk Float Freedom Inverter/Charger ConfigurationSetting Battery Types on the Main Unit Setting Absorption Switch 1SwitchViewing Inverter/Charger Information Adjusting Feature Settings ScreenTo change the charger’s charging current setting To change the inverter mode setting To adjust the low battery shutdown setting Freedom Inverter/Charger Operation Display Panel OperationFreedom Inverter/Charger Operation Operating in Shore Power Mode Operating in Inverter ModeInverter Mode Setting is on Standby Inverter Mode Setting is OFF Energy Saver 25-hour Automatic Shut OffaStatus LED During Inverter Mode LEDTurning the Audible Alarm on or OFF Checking Battery StatusChecking Output Power Operating Several Loads at OnceTransitioning from Shore Power to Inverter Mode Transitioning from Inverter Mode to Shore PowerPower Output Operating LimitsInput Voltage Operating Voltage Range Comment Condition Freedom HF Only Overload Conditions Over-temperature ConditionsInverter Loads High Surge Loads Trouble Loads Equipment DamageBattery Charging VoltageBattery Charging Flooded 14.4 13.5 Routine Maintenance Freedom HF UnitBatteries Inverter Overload Operation Invert Power Derating vs. Ambient Temperature Invert Power Derating vs. Ambient Temperature Troubleshooting Electrical Shock and Energy HazardCommon Problems Buzz in Audio EquipmentTelevision Reception Error Code Condition Mode Action  For error codes  to  Troubleshooting Reference Problem Possible Cause SolutionAC shore power is not available or out Inverter was probably damaged due to the reverse Problem Possible Cause Solution Motor Loads Inverter ApplicationsResistive Loads Long Transfer TimesSpecifications Watt models 1800-watt modelsDC Input AC Input Page Page Schneider Electric Solar Inverters USA Inc
Related manuals
Manual 64 pages 12.33 Kb