Xantrex Technology 806-1544, 806-1840 Operating Voltage Range Comment Condition Freedom HF Only

Page 37

Freedom HF InvChg Owners Guide.book Page 23 Tuesday, April 29, 2014 12:10 PM

Operating During Transition Between Shore Power and Inverter Mode

The allowable Freedom HF input voltage ranges are shown in the following table for Freedom HF 1500 and Freedom HF 1800 T:

 

 

Operating

Voltage Range

Voltage Range

Comment

 

 

 

 

Condition

Freedom HF

Freedom HF

 

 

 

 

 

 

 

 

 

 

 

 

1500 only

1800 T only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Operating

Low, Mid, High:

Low:

Low refers to low limit of the low

 

 

 

 

 

 

 

 

Range

12.1–15.5 volts

10.5–15.5 volts

voltage threshold.

 

 

 

 

 

 

 

Mid:

Mid refers to middle limit of the low

 

 

 

 

 

 

 

11.8–15.5 volts

voltage threshold.

 

 

 

 

 

 

 

High:

High refers to high limit of the low

 

 

 

 

 

 

 

12.1–15.5 volts

voltage threshold.

 

 

 

 

Optimum

12.1–13.0 volts

12.1–13.0 volts

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

 

 

 

 

 

Low Voltage

Low, Mid, High:

Low: <11.0 volts

A silent low battery warning shows

 

 

 

 

 

 

 

 

Alarm

<12.6 volts

Mid: <12.3 volts

fault code  on the display.

 

 

 

 

 

 

 

High:<12.6 volts

 

 

 

 

 

 

 

 

 

 

Low Voltage

Low, Mid, High:

Low: <10.5 volts

A single one-second low battery

 

 

 

 

 

 

 

 

Shutdown

<12.1 volts

Mid: <11.8 volts

alarm beeps and the display shows

 

 

 

 

 

 

 

High:<12.1 volts

fault code . After five minutes,

 

 

 

 

 

 

 

 

the unit shuts down completely.

 

 

 

 

Instant Low

<10.2 volts

<10.2 volts

After two seconds below the limit,

 

 

 

 

 

 

 

 

Voltage

 

 

the unit shuts down and the low

 

 

 

 

Shutdown

 

 

battery alarm sounds a long beep

 

 

 

 

 

 

 

 

continuously for 30 seconds.

 

 

 

 

High Voltage

15.5 volts or

15.5 volts or

The over-voltage alarm beeps every

 

 

 

 

 

 

 

 

Shutdown

more

more

second and the display shows fault

 

 

 

 

 

 

 

 

code  alternating with the battery

 

 

 

 

 

 

 

 

voltage. The status LED turns red and

 

 

 

 

 

 

 

 

the display screen is turned OFF

 

 

 

 

 

 

 

 

within 30 seconds to protect itself

 

 

 

 

 

 

 

 

from excessive input voltage.

 

 

 

 

 

 

 

 

NOTE: Although the Freedom HF

 

 

 

 

 

 

 

 

incorporates over-voltage protection,

 

 

 

 

 

 

 

 

it can still be damaged if input

 

 

 

 

 

 

 

 

voltage exceeds 16 volts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

975-0390-01-01

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 37
Contents Freedom HF Inverter/Chargers Page Document Part Number Exclusion for DocumentationDate and Revision Product NumbersPurpose About This GuideConventions Used ScopeRelated Information Electrical Shock Hazard Important Safety InstructionsFire and Burn Hazard Precautions When Working With Batteries Exposure to Chemicals and Gases Hazard Regulatory Precautions for Using Rechargeable AppliancesKKK Information to the User FCC Information to the UserPage Contents Page Materials List IntroductionKey Features Low Mid High ModelDefault Setting Your Setting FeaturesFeature Description Front Panel Freedom HF 1000, 1055, 1500Front Panel Freedom HF 1055 EMS,1800 EMS Front Panel Freedom HF 1800 TSerial number of your unit Freedom HF 1055 EMS,1800 EMS Display Panel All Models Remote and Power Module PanelSide Panel All Models Setting Battery Types on the Main Unit Freedom Inverter/Charger ConfigurationBattery Dip Switch Bulk Float Setting Absorption Switch 1SwitchViewing Inverter/Charger Information Screen Adjusting Feature SettingsTo change the charger’s charging current setting To change the inverter mode setting To adjust the low battery shutdown setting Display Panel Operation Freedom Inverter/Charger OperationFreedom Inverter/Charger Operation Operating in Inverter Mode Operating in Shore Power ModeInverter Mode Setting is on Standby Energy Saver 25-hour Automatic Shut Offa Inverter Mode Setting is OFFLED Status LED During Inverter ModeChecking Output Power Checking Battery StatusTurning the Audible Alarm on or OFF Operating Several Loads at OnceTransitioning from Inverter Mode to Shore Power Transitioning from Shore Power to Inverter ModeOperating Limits Power OutputInput Voltage Operating Voltage Range Comment Condition Freedom HF Only Inverter Loads Over-temperature ConditionsOverload Conditions High Surge LoadsEquipment Damage Trouble LoadsVoltage Battery ChargingBattery Charging Flooded 14.4 13.5 Freedom HF Unit Routine MaintenanceBatteries Inverter Overload Operation Invert Power Derating vs. Ambient Temperature Invert Power Derating vs. Ambient Temperature Electrical Shock and Energy Hazard TroubleshootingBuzz in Audio Equipment Common ProblemsTelevision Reception  Error Code Condition Mode Action For error codes  to  Problem Possible Cause Solution Troubleshooting ReferenceAC shore power is not available or out Inverter was probably damaged due to the reverse Problem Possible Cause Solution Resistive Loads Inverter ApplicationsMotor Loads Long Transfer TimesWatt models 1800-watt models SpecificationsDC Input AC Input Page Page Schneider Electric Solar Inverters USA Inc