1.Make sure that the UPS is properly installed and secured with its leveling feet.

2.Roll the battery cabinet to a spot near the right-hand side of the UPS, as shown in Figure 7.

3.The field kit is attached with cable ties to the frame inside the door. Remove and retain the field kit for later use.

4.If necessary, remove the cosmetic covers and hanger brackets from the right-hand side of the UPS. Save covers, screws, and brackets for later reuse.

5.Push the battery cabinet toward the UPS cabinet until the doors are flush with each other.

6.Three cabinet attachment brackets are provided for securing each cabinet at the top and bottom. Two flat brackets join the tops of the cabinets, one at the front and one at the back. A larger flat bracket joins the cabinets at the bottom. Attach the flat brackets to the cabinet tops first.

7.For Series 685 Battery Cabinets, remove the right-hand screw from the top right door hinge of the UPS cabinet. Align the hole in one flat bracket over this screw hole, and the other hole over the hole in the top of the battery cabinet. Replace the screw in the hinge, and attach the other end of the bracket to the top of the battery cabinet using an M4×10 hex screw from the field kit (see Figure 7).

8.For Series 1085 Battery Cabinets, remove the right-hand screw from the top right door hinge of the UPS cabinet, and the right-hand screw from the top left door hinge of the battery cabinet. Align the holes in the flat bracket over these screw holes and then replace the screws in the hinges (see Figure 7).

9.Align the holes in the other small flat bracket with the two holes in the top rear of the UPS and the battery cabinet. Attach each end to its mating hole using an M4×10 hex screw from the field kit (see Figure 7).

NOTE: Perform Steps 10 through 13 for the Series 1085 Battery Cabinet. Perform Steps 14 through 18 for the Series 685 Battery Cabinet.

10.Locate the large flat bracket from the field kit. Place one end of the bracket over the stud on the bottom side of the UPS cabinet lower right-hand hinge, and the other end over the stud on the bottom side of the lower right-hand hinge on the Series 1085 Battery Cabinet (see Figure 8).

11.Attach the bracket to the hinges with two M8 self-locking nuts from the field kit.

12

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

 

Installation Manual 164201408 Rev. P00 053002

Image 18
Contents Series 685 Auxiliary Battery Cabinets Important Safety Instructions General Notes About Installing Battery Cabinets Conventions Used in This Manual Table of Contents Typical Battery Cabinets Typical Battery Cabinets IntroductionIdentification of Your Battery System UPSBattery Cabinets For More Information Getting HelpPreparing Your Site Unpacking Your Battery CabinetPreparing for Wiring the Battery Cabinet Environmental ConsiderationsInspecting and Unpacking Each Cabinet Outer Packaging PLY---FOAM CushionsUnloading the Battery Cabinet from the Pallet Removing Front and Rear Supports Creating an Installation Plan Page Connecting to Powerware 9350 30 Powerware 9350 UPS with Integral Battery CabinetsInstallation Manual 164201408 Rev. P00 See for Series TOP View Front View Attaching UPS Base to Series 685 Base Installation Manual 164201408 Rev. P00 Series 685 Battery Cabinet Wiring Detail Series 685 Cabinet Series 1085 Battery Cabinet Wiring Detail Powerware 9350 UPS with Separately Located Battery Cabinets UPS with Separately Located Battery CabinetsSeparate Installation of Series 685 Battery Cabinets Connecting Two Series 685 Bases Separate Installation of Series 1085 Battery Cabinets Connecting Two Series 1085 Bases To Electrically Connect Separate Battery Cabinets to the UPS Installation Manual 164201408 Rev. P00 Completing the Installation Checklist Installation Checklist for Powerware 9350 30 throughThis Page Intentionally Left Blank Connecting to Powerware 9350 ---80 Battery Connections for a PowerwarePowerware 9350---80 or 160 with Separate Battery Cabinets Completing the Installation Checklist Installation Checklist for Powerware Installing a Remote Battery Disconnect Remote Battery Disconnect Enclosure31.1 N-M 255---275 lb-in Table A. Remote Battery Disconnect Power Terminations Table C. Remote Battery Disconnect Circuit Breaker Ratings Series 685 / 1085 Configurations Appendix a --- Customer InformationIntegral Tool Size Torque Battery Cabinet UPS Cabinet 375 200 Type Series 685 Battery Cabinet TOP View Series 1085 Battery Cabinet Series 1085 Battery Cabinet plan TB1 164201408--4 This Page Intentionally Left Blank