1.The output of the UPS is a separately derived source. Output neutral is bonded to equipment ground through the main bonding jumper. Refer to NEC Article 250 and local codes for proper grounding practices.
2.Your battery cabinet operating environment must meet the size and weight requirements shown in Table A:
Table A. Equipment Weight and Point Loading (on casters)
(4 leveling feet are provided)
| Weight | Point Loading |
Component | Kg (lb) | Kg (lb) |
Series | 869 (1915) | 4 at 217 (479) |
|
|
|
Series | 1111 (2450) | 4 at 278 (613) |
|
|
|
Series | 1429 (3150) | 8 at 179 (394) |
|
|
|
Series | 1588 (3500) | 8 at 199 (438) |
|
|
|
Series | 1708 (3765) | 8 at 214 (471) |
|
|
|
Series | 2178 (4800) | 8 at 272 (600) |
3.The basic environmental requirements for operation of the battery system are:
Ambient Temperature Range: | 40˚C | 104˚F) | |
Recommended Operating Range: | 25˚C | 77˚F) | |
Maximum Relative Humidity: | 95% noncondensing |
4.Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control wiring in separate conduit from the power wiring. The wire should be rated at 24 volts, 1 amp minimum.
5.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 1.8 volts per cell.
6.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.
7.A battery disconnect switch is recommended, and may be required by NEC or local codes when batteries are separately located. The battery disconnect switch may be supplied as an accessory, and should be installed between the battery and the UPS.
8.If the conductors used for DC input from the battery cabinet(s) to the UPS are those provided by the UPS manufacturer, and the UPS and battery cabinet are manufactured by the same supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.
Table B. External Ground Wire Requirements for Battery Cabinets
|
|
|
| Integral |
| Tool Size | Torque | |
UPS | Battery | Battery | # of | or | Wire Size | |||
Battery | ||||||||
Model | Series | Type | Cabinets | Separate | Battery | |||
Cabinet | ||||||||
|
|
|
| Battery |
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
all | 685 or 1085 | all | all | all | 1/0 | 7/16I slot | 5.6 (50) | |
|
|
|
|
|
|
|
|
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets | |