Powerware 685, 1085 installation manual Installation Manual 164201408 Rev. P00

Page 22

To Electrically Connect Integral Battery Cabinets Together and to the UPS:

1.All battery cabinets will arrive at your site with each battery connection string electrically disconnected. If you are installing more than one battery cabinet, perform Steps 2 through 6 for each cabinet. The battery cabinet adjacent to the UPS will be the only cabinet directly connected to the UPS.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE REMAINING

STEPS IN THIS SECTION AND SUBSEQUENT SECTIONS.

2.After making sure that all battery breakers are in the OFF position, connect the string of battery trays together by mating the loose red connector from each tray to the fixed black connector mounted on the front edge of the tray above it (see Figure 10 for Series 685 and Figure 13 for Series 1085).

3.Find the red (positive) and black (negative) cables supplied coiled inside the cabinet. These cables are provided half-stripped to facilitate attaching to the lugs in the cabinet. Use double pole compression lugs to secure the wires to the unit terminal blocks.

4.Wire the UPS to the Battery cabinet by attaching the provided cable from E4(+) to “DC+” and E5(---) to “DC---” power interconnection cables provided. The provided red(+) and black(---) cables are already cut to length.

5.Remove the cable tie securing the battery breaker sensing cable.

6.Locate the battery breaker sensing cable in the right-hand Battery cabinet. Route this connector into the cabinet to the immediate left and mate with the matching connector in the bottom of that cabinet. Connect all battery cabinets together this way.

7.Locate control harness with semi-stripped ends in Battery cabinet. Connect this to the CUSTTB terminal strip in the UPS. Route the battery cable to the immediate right and mate with the matching connector in the bottom of the UPS cabinet.

8.Repeat Steps 2 through 7 for each battery cabinet to be joined.

9.Mount the side panel to the side of the right-hand battery cabinet:

a.Mount the hanger brackets to the top side of the right-hand battery cabinet using M4 screws (see Figure 11).

b.Hang the side panel on the hanger brackets and align with the front and rear of the battery cabinet.

c.Secure the side panel at the bottom using M4 hex head screws.

10.Secure all battery cabinets by closing and latching the doors.

11.Secure the UPS by reinstalling safety shields and closing and latching the doors.

16

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

 

Installation Manual 164201408 Rev. P00 053002

Image 22
Contents Series 685 Auxiliary Battery Cabinets Important Safety Instructions General Notes About Installing Battery Cabinets Conventions Used in This Manual Table of Contents Typical Battery Cabinets Typical Battery Cabinets IntroductionIdentification of Your Battery System UPSBattery Cabinets For More Information Getting HelpPreparing Your Site Unpacking Your Battery CabinetPreparing for Wiring the Battery Cabinet Environmental ConsiderationsInspecting and Unpacking Each Cabinet Outer Packaging PLY---FOAM CushionsUnloading the Battery Cabinet from the Pallet Removing Front and Rear Supports Creating an Installation Plan Page Connecting to Powerware 9350 30 Powerware 9350 UPS with Integral Battery CabinetsInstallation Manual 164201408 Rev. P00 See for Series TOP View Front View Attaching UPS Base to Series 685 Base Installation Manual 164201408 Rev. P00 Series 685 Battery Cabinet Wiring Detail Series 685 Cabinet Series 1085 Battery Cabinet Wiring Detail Powerware 9350 UPS with Separately Located Battery Cabinets UPS with Separately Located Battery CabinetsSeparate Installation of Series 685 Battery Cabinets Connecting Two Series 685 Bases Separate Installation of Series 1085 Battery Cabinets Connecting Two Series 1085 Bases To Electrically Connect Separate Battery Cabinets to the UPS Installation Manual 164201408 Rev. P00 Completing the Installation Checklist Installation Checklist for Powerware 9350 30 throughThis Page Intentionally Left Blank Connecting to Powerware 9350 ---80 Battery Connections for a PowerwarePowerware 9350---80 or 160 with Separate Battery Cabinets Completing the Installation Checklist Installation Checklist for Powerware Installing a Remote Battery Disconnect Remote Battery Disconnect Enclosure31.1 N-M 255---275 lb-in Table A. Remote Battery Disconnect Power Terminations Table C. Remote Battery Disconnect Circuit Breaker Ratings Series 685 / 1085 Configurations Appendix a --- Customer InformationIntegral Tool Size Torque Battery Cabinet UPS Cabinet 375 200 Type Series 685 Battery Cabinet TOP View Series 1085 Battery Cabinet Series 1085 Battery Cabinet plan TB1 164201408--4 This Page Intentionally Left Blank