4 Cabinets Maximum
(E4)
(E5)
UPS BATTERY BATTERY CABINET CABINET CABINET
Powerware 9350 30 through 160 Battery Cabinets integral to UPS
and connected using Manufacturer supplied wiring
CONTRACTOR | CONTRACTOR |
WIRING (1) | WIRING (2) |
(E4)
(E5)
4 Cabinets Maximum
BATTERY
DISCONNECT
UPS | BATTERY | BATTERY | |||||||
CABINET | CABINET | CABINET | |||||||
|
|
|
|
|
|
|
|
|
|
Powerware 9350 30 through 160 Battery Cabinets located separately from the UPS
NOTE: The term “Separate” refers to battery cabinets that are not physically attached to the UPS, are wired with external contractor supplied wiring, and use a single overcurent protection and disconnect device located near the batteries.
The term “Integral” refers to battery cabinets that are physically attached to the UPS and the wiring between them is internal. The power wiring is supplied with the system, and they use the UPS battery switch as the battery isolation device.
The wire size rating for products up to and including the 160/160 are for the total battery supply. Since these UPS units can only land one wire per DC connection point, a common DC collector including an isolation device and overcurrent protection should be used. Refer to applicable national or local code requirements for your installation.
| Contractor Wiring (1): Refer to UPS manual to size wiring |
|
|
| ||
| Contractor Wiring (2): See |
|
|
|
|
|
| Table C of Appendix A to size | DESCRIPTION: | Series 685 / 1085 Configurations |
|
| |
| Contractor Supplied wiring |
|
|
|
|
|
| DRAWING NO: |
| SHEET: | 1 of 1 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets |
| ||||
| Installation Manual 164201408 Rev. P00 053002 |
|
|
|
|