Powerware 1085, 685 To Electrically Connect Separate Battery Cabinets to the UPS

Page 31

To Electrically Connect Separate Battery Cabinets to the UPS:

1.All battery cabinets will arrive at your site with each battery connection string electrically disconnected. If you are installing more than one battery cabinet, perform Steps 2 through 6 for each cabinet. Battery cabinet #1 (the left-hand cabinet) will be the only cabinet directly connected to the UPS.

WARNING:

LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE REMAINING

STEPS IN THIS SECTION AND SUBSEQUENT SECTIONS.

2.After making sure that all battery breakers are in the OFF position, connect the string of battery trays together by mating the loose red connector from each tray to the fixed black connector mounted on the front edge of the tray above it (see Figure 10 for Series 685 and Figure 13 for Series 1085 for location of all items discussed in this section).

3.Find the red (positive) and black (negative) cables supplied coiled inside the cabinet. These cables are provided half-stripped to facilitate attaching to the lugs in the cabinet. Use double pole compression lugs to secure the wires to the unit terminal blocks.

4.Remove the cable tie securing the battery breaker sensing cable.

5.Locate the battery breaker sensing cable in the right-hand battery cabinet. Route this connector into the cabinet to the immediate left and mate with the matching connector in the bottom of that cabinet. Connect all battery cabinets together this way.

6.Repeat Steps 2 through 5 for each battery cabinet to be joined.

7.Route cables from positive (+) and negative (---) terminals in the bottom of battery cabinet #1 through conduit (top or bottom entry) to terminals E4 and E5 of the UPS cabinet. See Figure 10 or Figure 12 for location of positive (+) and negative (---) terminals.

a.Refer to Appendix A, Table C to size wire for connecting the battery cabinets to the remotely located UPS cabinet.

b.See Drawing 164201408---1 in Appendix A for Series 685 Battery Cabinet top or bottom conduit landing locations.

c.See Drawing 164201408---2 in Appendix A for Series 1085 Battery Cabinet top or bottom conduit landing locations.

d.See Installation Manual 164200253 for Powerware 9350 30---80 kVA top or bottom conduit landing locations.

e.See Installation Manual 164200292 for Powerware 9350 100---160 kVA top or bottom conduit landing locations. The conduit landing plates are removable to add conduit landing holes as required. The conduit landing plates should be removed when holes are added to keep metal particles from falling inside the battery cabinet.

f.Refer to Chapter 5, Table C for remote battery disconnect circuit breaker information.

 

 

 

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

25

Installation Manual 164201408 Rev. P00 053002

 

 

Image 31
Contents Series 685 Auxiliary Battery Cabinets Important Safety Instructions General Notes About Installing Battery Cabinets Conventions Used in This Manual Table of Contents Typical Battery Cabinets Introduction Typical Battery CabinetsUPS Identification of Your Battery SystemBattery Cabinets Getting Help For More InformationEnvironmental Considerations Unpacking Your Battery CabinetPreparing for Wiring the Battery Cabinet Preparing Your SiteOuter Packaging PLY---FOAM Cushions Inspecting and Unpacking Each CabinetUnloading the Battery Cabinet from the Pallet Removing Front and Rear Supports Creating an Installation Plan Page Powerware 9350 UPS with Integral Battery Cabinets Connecting to Powerware 9350 30Installation Manual 164201408 Rev. P00 See for Series TOP View Front View Attaching UPS Base to Series 685 Base Installation Manual 164201408 Rev. P00 Series 685 Battery Cabinet Wiring Detail Series 685 Cabinet Series 1085 Battery Cabinet Wiring Detail UPS with Separately Located Battery Cabinets Powerware 9350 UPS with Separately Located Battery CabinetsSeparate Installation of Series 685 Battery Cabinets Connecting Two Series 685 Bases Separate Installation of Series 1085 Battery Cabinets Connecting Two Series 1085 Bases To Electrically Connect Separate Battery Cabinets to the UPS Installation Manual 164201408 Rev. P00 Installation Checklist for Powerware 9350 30 through Completing the Installation ChecklistThis Page Intentionally Left Blank Battery Connections for a Powerware Connecting to Powerware 9350 ---80Powerware 9350---80 or 160 with Separate Battery Cabinets Completing the Installation Checklist Installation Checklist for Powerware Remote Battery Disconnect Enclosure Installing a Remote Battery Disconnect31.1 N-M 255---275 lb-in Table A. Remote Battery Disconnect Power Terminations Table C. Remote Battery Disconnect Circuit Breaker Ratings Appendix a --- Customer Information Series 685 / 1085 ConfigurationsIntegral Tool Size Torque Battery Cabinet UPS Cabinet 375 200 Type Series 685 Battery Cabinet TOP View Series 1085 Battery Cabinet Series 1085 Battery Cabinet plan TB1 164201408--4 This Page Intentionally Left Blank