Completing the Installation Checklist

The final step in installing your battery cabinet is to complete the Installation Checklist. This checklist ensures that you have installed all hardware, cables, and other equipment. Completing all items on the checklist will ensure a smooth installation. Make a copy of the Installation Checklist before filling it out, and retain the original.

After completing your installation, a service representative will be able to verify the operation of your battery cabinet, and commission it to support your critical load. The service representative cannot perform any installation tasks other than verifying that the battery cabinet has been correctly installed. Service personnel may request a copy of the completed Installation Checklist to be sure you have completed all applicable equipment installation requirements.

NOTE:

The Installation Checklist MUST be completed prior to starting up the UPS system for the first time.

Installation Checklist for Powerware 9350 30 through 160

-All packing materials and restraints have been removed from each cabinet.

-Each cabinet in the battery system is placed in its correct location.

-All cabinets are bolted together.

-A ground wire is installed between all cabinets that are bolted together.

-All conduits and cables are properly routed to the battery cabinets.

-A ground conductor is properly installed.

-Battery cables and harness are terminated on the K2 battery contactor E4 and E5 in the UPS cabinet.

-Internal battery cabinet connections have been completed (bus bars, plugs, etc.)

-Air conditioning equipment is installed and operating correctly.

-The area around the installed battery system is clean and dust-free.

(It is recommended that the battery cabinet be installed on a sealed concrete pad or a sealed concrete floor.)

-Adequate working area exists around the battery cabinet and other cabinets.

-Adequate lighting is provided around all battery cabinet equipment.

-A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the battery cabinet (OPTIONAL).

 

 

 

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

27

Installation Manual 164201408 Rev. P00 053002

 

 

Image 33
Contents Series 685 Auxiliary Battery Cabinets Important Safety Instructions General Notes About Installing Battery Cabinets Conventions Used in This Manual Table of Contents Typical Battery Cabinets Introduction Typical Battery CabinetsUPS Identification of Your Battery SystemBattery Cabinets Getting Help For More InformationPreparing for Wiring the Battery Cabinet Unpacking Your Battery CabinetPreparing Your Site Environmental ConsiderationsOuter Packaging PLY---FOAM Cushions Inspecting and Unpacking Each CabinetUnloading the Battery Cabinet from the Pallet Removing Front and Rear Supports Creating an Installation Plan Page Powerware 9350 UPS with Integral Battery Cabinets Connecting to Powerware 9350 30Installation Manual 164201408 Rev. P00 See for Series TOP View Front View Attaching UPS Base to Series 685 Base Installation Manual 164201408 Rev. P00 Series 685 Battery Cabinet Wiring Detail Series 685 Cabinet Series 1085 Battery Cabinet Wiring Detail UPS with Separately Located Battery Cabinets Powerware 9350 UPS with Separately Located Battery CabinetsSeparate Installation of Series 685 Battery Cabinets Connecting Two Series 685 Bases Separate Installation of Series 1085 Battery Cabinets Connecting Two Series 1085 Bases To Electrically Connect Separate Battery Cabinets to the UPS Installation Manual 164201408 Rev. P00 Installation Checklist for Powerware 9350 30 through Completing the Installation ChecklistThis Page Intentionally Left Blank Battery Connections for a Powerware Connecting to Powerware 9350 ---80Powerware 9350---80 or 160 with Separate Battery Cabinets Completing the Installation Checklist Installation Checklist for Powerware Remote Battery Disconnect Enclosure Installing a Remote Battery Disconnect31.1 N-M 255---275 lb-in Table A. Remote Battery Disconnect Power Terminations Table C. Remote Battery Disconnect Circuit Breaker Ratings Appendix a --- Customer Information Series 685 / 1085 ConfigurationsIntegral Tool Size Torque Battery Cabinet UPS Cabinet 375 200 Type Series 685 Battery Cabinet TOP View Series 1085 Battery Cabinet Series 1085 Battery Cabinet plan TB1 164201408--4 This Page Intentionally Left Blank