ATTENTION:
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incen- die. Suivre les précautions qui s’imposent.
•Pour le remplacement, utiliser le même nombre et modéle des batteries.
•L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.
General Notes About Installing Battery Cabinets
Each battery cabinet is packed and crated separately for shipping. You should unpack and inspect each cabinet, roll it to its final position, and join it to the UPS or other cabinets (refer to Chapter 3 or Chaper 4) before installing wiring.
These general installation notes apply to either the Series 685 Battery Cabinet or the Series 1085 Battery Cabinet:
•Do not tilt battery cabinets more than 10˚ during installation.
•The recommended minimum clearance over each battery cabinet is 305 mm (12 in.).
•The conduit landing plates are removable to add conduit landing holes as required. The conduit landing plates should be removed when holes are added to keep metal particles from falling inside the battery cabinet. Plate material is 16 gauge steel (1.5 mm, 0.06 in. thick).
•Low voltage signal wiring must be installed in a separate conduit from the power wiring.
•Each battery cabinet can be installed as a
•The instantaneous trip circuit breakers for the Series 685 and Series 1085 Battery Cabinets must remain set at minimum (full counterclockwise).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets | iii |
Installation Manual 164201408 Rev. P00 053002 |
|