OTHER SETPOINTS THAT MIGHT BE REQUIRED FOR MOTOR PID CONTROL

Max Change Rate = The VFD motor PID output is limited by this parameter to prevent large instantaneous changes to the motor speed.

Dead-band= used to establish a range on either side of the set-point in which no capacity control action will occur. Initial Setpoint: 2.5%

Min Spd Point = used to prevent the compressor from running too slowly which can adversely affect hydro- dynamic sealing, heat transfer and lubrication. Initial Setpoint: 50%

Setpoint Ramping Rate = used to control how fast the compressor responds to the required capacity control action. Initial Setpoint: 20 Unit/min

Unloading Rate = used to control how fast the unloading action occurs due to a safety override. Initial Set- point: 20%/min

31

Image 31
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Voltage Source Proper Wire SizingVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Main Screen Touch Screen LCD DisplayMenu Button LOG on Button IndicatorsMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Problem Reason Solution Slide Valve Trouble Shooting GuideProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Suction Pressure SP#2 Fail Percent Volume FailLow Control Temperature Fail Suction Pressure SP#1 FailLow Oil Injection Temp Fail Auxiliary Safety#1 Input FailLow Start Oil Pressure Fail Low Oil Pressure FailVission 20/20 Troubleshooting Guide Digital & Analog Boards DipswitchesDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com