OTHER SETPOINTS THAT MIGHT BE REQUIRED FOR MOTOR PID CONTROL
•Max Change Rate = The VFD motor PID output is limited by this parameter to prevent large instantaneous changes to the motor speed.
•
•Min Spd Point = used to prevent the compressor from running too slowly which can adversely affect hydro- dynamic sealing, heat transfer and lubrication. Initial Setpoint: 50%
•Setpoint Ramping Rate = used to control how fast the compressor responds to the required capacity control action. Initial Setpoint: 20 Unit/min
•Unloading Rate = used to control how fast the unloading action occurs due to a safety override. Initial Set- point: 20%/min