Trend Chart

This screen allows the operator to view and adjust settings for the trend chart.

The trend analysis screen shows recorded data for problem analysis or tuning improvements. A logging buffer holds 30 minutes of data for 13 variables sampled at 10 second intervals. When the logging buffer fills with 30 minutes of data, it is automatically transferred to a file, which will can up to 120 hours of accumulated data. When the file has accumulated 120 hours of data, and the logging buffer has filled with another 30 minutes of data, the oldest data in the file is dumped, and the newest 30 minute data is added to the file.

When the trend chart screen is opened, this logging data is copied to a display buffer and logging continues un- interrupted. The data available for display in this display buffer is 120 hours maximum. The sample of data in the display buffer is not altered by selection of a different variable to view. It is only discarded when the user exits the trend chart screen, or when the control is powered down.

Up to 4 variables can be selected for plotting at one time. Each is assigned one of 4 colors - the plotted trace and the vertical axis labels for a variable will be in its assigned color. You can move from viewing the plot to selecting which variables and time interval to show as often as necessary. A start and stop button allows you to stop the trending if desired. When the stop button is pressed, you are asked to provide a name for a file which will contain the saved trend data. A Trace button and a Hold button allows you to move a cursor line across all four trend lines and receive a readout of all four variables at the point in time of the cursor position. The hold button stops the data from advancing on the display - but doesn’t stop the background trending.

The vertical axis scaling and offset for each variable plotted is based on its range of values over the entire display buffer sample. This helps to magnify small changes in a variable and to keep one plot trace from falling on top of another, but it can be misleading. Look at the range of the vertical axis for a variable and try to visualize how far off screen the zero point would be.

53

Image 53
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Voltage Source Proper Wire SizingVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Menu Button Touch Screen LCD DisplayMain Screen LOG on Button IndicatorsMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Problem Reason Solution Slide Valve Trouble Shooting GuideProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Low Control Temperature Fail Percent Volume FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailLow Start Oil Pressure Fail Auxiliary Safety#1 Input FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Digital & Analog Boards DipswitchesDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com