Emerson VISSION 20/20 service manual Misc. Control

Page 34

Additional Control Setpoints

Misc. Control

Control Mode = Drop-down box allows selection of current operating mode, from the list of allowable modes.

High Motor Amps (Unloading) = This control feature will limit the compressor capacity when the compressor motor amps reaches these load limiting set-points. When the set-points are set properly, this control feature will prevent the motor from operating at excessive high amp conditions, which will help to prevent the com- pressor starter from stopping the compressor on “motor overload” conditions.

Stop Load = prevents the compressor from loading when the set-point is reached. For a 1.15 SF motor, this value is the FLA value stamped onto the motor nameplate.

Force Unload = forces an unload condition when this set-point is reached. For a 1.15 SF motor, this value is FLA value (from motor nameplate) x 1.15. The unload pulse is released when the motor amps lands just above the FLA setting.

High Discharge Pressure (Unloading) = This control feature is active in Suction Pressure or Process Tempera- ture Capacity Control mode. This control feature will limit the compressor from loading when the compressor discharge pressure reaches these load limiting conditions. When the set-points are set properly, this control feature will prevent the compressor from experiencing excessive high discharge pressure that could result in a high discharge pressure failure. The high discharge pressure unloading set-points over-ride the Suction Pres- sure or Process Temperature Capacity Control Set-points.

34

Image 34
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Main Screen Touch Screen LCD DisplayMenu Button Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Suction Pressure SP#1 Fail Percent Volume FailLow Control Temperature Fail Suction Pressure SP#2 FailLow Oil Pressure Fail Auxiliary Safety#1 Input FailLow Start Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com