Page 38

Low Suction Pressure Alarm and Trip = This is the low suction pressure safety. This safety is active in both temperature and pressure control modes. An alarm or trip will be active on a drop in suction pressure at or below the set-point value.

High Discharge Pressure Alarm and Trip = This is the high discharge pressure safety. The alarm or trip will be active on a rise in discharge pressure at or above the set-point value.

High Process Temperature Alarm = This alarm is active when the process temperature is at or above the set- point value. There is no TRIP set-point.

Low Process Temperature Alarm and Trip = This is the low control temperature safety. This safety is active when process temperature control has been selected in the Control Mode dropdown selection found in the Compres- sor Control Menu. An alarm or trip will be active on a drop in process temperature below the set-point value.

38

Image 38
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Menu Button Touch Screen LCD DisplayMain Screen Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Suction Pressure SP#1 Fail Percent Volume FailLow Control Temperature Fail Suction Pressure SP#2 FailLow Oil Pressure Fail Auxiliary Safety#1 Input FailLow Start Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com