Emerson VISSION 20/20 service manual Time Proportioning Control

Page 29

TIME PROPORTIONING CONTROL

Assume that Suction Pressure is the selected parameter to control compressor capacity. Time proportioning control is the method used to control the compressor slide valve position in response to a setpoint.

The setpoints are;

 

• Pressure Control Setpoint

(This is the target set-point.)

Proportional band

Dead-band

Interval time

Example:

Setpoint = 20 psig

High Proportional Band = 4 psig

High Dead-band region = 4 x 0.10 = 0.4 psig Low Proportional Band = 3 psig

Low Dead-band region = 3 x 0.10 = 0.3 psig

Proportional Band

When the suction pressure exceeds the dead-band in either direction, it then enters the “proportional band” area. The Capacity Increase/Decrease Proportional Band defines the range of pressure in which corrective action will be taken to bring the suction pressure back to within the setpoint dead-band. This is done by pulsing the appropriate capacity motor. The length of the pulse is in direct proportion to the amount of deviation that the suction pressure is from the setpoint dead-band.

Dead Band

A region around the setpoint automatically exists and defines a range around the setpoint where the pressure is allowed to deviate without the program taking any corrective action. This allows small variances of pressure around the setpoint, and reduces capacity hunting from occurring. The dead-band regions are always defined as 10% of the proportional band region values.

Interval Time

The Capacity Increase/Decrease Interval Time is the time interval that the program will use to look and determine if a capacity increase or decrease pulse is required to bring the Suction Pressure back to the setpoint dead-band area. The length of the pulse is in direct proportion to the amount of deviation that the suction pressure is from the setpoint dead-band. The formula used to determine the length of pulse is described as:

0.5 second pulse for every 10% away from dead-band region.

0 second pulse = suction pressure within set-point dead-band

0.5 second pulse = suction pressure is in the proportional band region and 10% or less from the dead-band region.

1 second pulse = suction pressure is in the proportional band region and is > 10% and < 20% from the dead- band region.

1.5 second pulse = suction pressure is in the proportional band region and is > 20% and < 30% from the dead- band region.

2 second pulse = suction pressure is in the proportional band region and is > 30% and < 40% from the dead- band region.

2.5 second pulse = suction pressure is in the proportional band region and is > 40% and < 50% from the dead- band region.

3 second pulse = suction pressure is in the proportional band region and is > 50% and < 60% from the dead- band region.

29

Image 29
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Voltage Source Proper Wire SizingVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Menu Button Touch Screen LCD DisplayMain Screen LOG on Button IndicatorsMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Problem Reason Solution Slide Valve Trouble Shooting GuideProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Low Control Temperature Fail Percent Volume FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailLow Start Oil Pressure Fail Auxiliary Safety#1 Input FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Digital & Analog Boards DipswitchesDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com