TIME PROPORTIONING CONTROL
Assume that Suction Pressure is the selected parameter to control compressor capacity. Time proportioning control is the method used to control the compressor slide valve position in response to a setpoint.
The setpoints are; |
|
• Pressure Control Setpoint | (This is the target |
•Proportional band
•
•Interval time
Example:
Setpoint = 20 psig
High Proportional Band = 4 psig
High
Low
Proportional Band
When the suction pressure exceeds the
Dead Band
A region around the setpoint automatically exists and defines a range around the setpoint where the pressure is allowed to deviate without the program taking any corrective action. This allows small variances of pressure around the setpoint, and reduces capacity hunting from occurring. The
Interval Time
The Capacity Increase/Decrease Interval Time is the time interval that the program will use to look and determine if a capacity increase or decrease pulse is required to bring the Suction Pressure back to the setpoint
•0.5 second pulse for every 10% away from
•0 second pulse = suction pressure within
•0.5 second pulse = suction pressure is in the proportional band region and 10% or less from the
•1 second pulse = suction pressure is in the proportional band region and is > 10% and < 20% from the dead- band region.
•1.5 second pulse = suction pressure is in the proportional band region and is > 20% and < 30% from the dead- band region.
•2 second pulse = suction pressure is in the proportional band region and is > 30% and < 40% from the dead- band region.
•2.5 second pulse = suction pressure is in the proportional band region and is > 40% and < 50% from the dead- band region.
•3 second pulse = suction pressure is in the proportional band region and is > 50% and < 60% from the dead- band region.
29