VRS OIL SOLENOID OUTPUT – Used in VRS retrofit applications where an oil solenoid is installed in the oil line.

COMP MOTOR STARTER AUXILIARY CONTACT – This input looks for a feedback signal from the compressor starter, confirming that the compressor starter is energized.

HIGH LEVEL SHUTDOWN INPUT – This input must be energized in order for the compressor to operate. If de-ener- gized, the compressor will shut down and issue a high level trip.

OIL LEVEL FLOAT SWITCH #1 INPUT – Used for Cool Compression.

OIL LEVEL FLOAT SWITCH #2 INPUT – Used for Cool Compression.

LOCAL/REMOTE SELECT INPUT – This input enables or disables remote I/O control. Energizing this input enables the Remote Capacity Increase and Remote Capacity Decrease inputs.

REMOTE START/STOP INPUT – If the compressor is enabled for remote I/O control, this input is enabled. Energiz- ing this input will issue a start for the compressor as long as it is available to run. De-energizing this input stops the compressor.

REMOTE CAPACITY INCREASE INPUT – If the compressor is enabled for remote I/O control, this input is enabled. Operational only when the compressor is running. Energizing this input will increase the slide valve position. The slide valve will continuously increase as long as this input is energized. The slide valve will not increase when this input is de-energized.

NOTE: The scan interval on the remote increase and decrease modules is approximately ONE SECOND. Please take that into account when developing a control scheme using the remote increase and remote decrease modules for compressor control.

REMOTE CAPACITY DECREASE INPUT – If the compressor is enabled for remote I/O control, this input is enabled. Operational only when the compressor is running. Energizing this input will decrease the slide valve position. The slide valve will continuously decrease as long as this input is energized. The slide valve will not decrease when this input is de-energized.

CONDENSER STEP #1 OUTPUT – This output is enabled when condenser control option is selected. A condenser fan or pump will be turned on or off by this output.

CONDENSER STEP #2 OUTPUT – This output is enabled when condenser control option is selected. A condenser fan or pump will be turned on or off by this output.

CONDENSER STEP #3 OUTPUT – This output is enabled when condenser control option is selected. A condenser fan or pump will be turned on or off by this output.

CONDENSER STEP #4 OUTPUT – This output is enabled when condenser control option is selected. A condenser fan or pump will be turned on or off by this output.

AUXILIARY #1 thru #8 INPUT – Optional inputs that can be configured as an alarm or trip. Typically connected to external switched devices.

20

Image 20
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Menu Button Touch Screen LCD DisplayMain Screen Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Percent Volume Fail Low Control Temperature FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailAuxiliary Safety#1 Input Fail Low Start Oil Pressure FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com