Emerson VISSION 20/20 service manual Pull-down

Page 33

Stop Delay = delays the compressor from stopping when the suction pressure is equal to or less than the stop pressure.

Minimum Slide Position = The minimum capacity slide position that the compressor is allowed to run at. By forcing the compressor capacity to operate at a value above minimum, we insure that the suction pressure will be pulled down to the Stop pressure setpoint value.

Pull-down

The Pull-down set-points define a method of slowly pulling the suction pressure down from a high value. This is sometimes required on systems that have liquid recirculation systems. On such systems, if the suc- tion pressure is pulled down too fast, the pumps can cavitate, causing vibration and damage to the pumps. Pull-down is also required for new plant startups. Pulling the temperature of new buildings down too quickly can cause structural damage, so limiting the suction pressure pull-down rate will prevent this, allowing time to de-humidify the rooms as the temperature in the rooms are pulled down.

The pull-down feature provides a method to slowly pull the suction pressure down to operating conditions. The pull-down method used is to step the suction pressure down over a defined time interval. When the time interval expires, another step is taken.

Example:

Assume the suction pressure is at 80 psig and the set-point we want to get to is 20 psig. This defines a change of 60 psig. We want to allow 48 hours of pull-down time. Pick a reasonable step pressure of 5 psig for every step.

Number of steps = (∆ 60 psig change * 1 step/5 psig) = 12 steps

Delay per step = (48 hours / 12 steps) = 4 hours/step

For the first 4 hours, the compressor runs at 75 psig. next 4 hours @ 70 psig

next 4 hours @ 65 psig

and so forth. After the 12th step (running at 25 psig), 48 hours will have elapsed, and the new setpoint be- comes 20 psig, achieving the 20 psig setpoint after 48 hours. After the pull-down setpoint equals or is less than the control setpoint, the pull-down feature disables itself.

Enable = Enables Pulldown control. Uncheck the box to disable the Pull-down setpoints.

Step Pressure = This setpoint defines the step increments which the suction pressure will be controlled at.

Delay Per Step = Defines the time increment at which the compressor will be controlled for each step.

33

Image 33
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Voltage Source Proper Wire SizingVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Touch Screen LCD Display Main ScreenMenu Button LOG on Button IndicatorsMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Problem Reason Solution Slide Valve Trouble Shooting GuideProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Low Control Temperature Fail Percent Volume FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailLow Start Oil Pressure Fail Auxiliary Safety#1 Input FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Digital & Analog Boards DipswitchesDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com