Emerson VISSION 20/20 service manual Pump-down

Page 32

Pump-Down and Pull-Down Setpoints

(For Future Software Releases)

Pump-down

The Pump-down set-points define a method of “pumping” down a chiller, which is to draw off refrigerant from the chiller. The purpose is to prevent liquid refrigerant from developing in the chiller during an off cycle, and then being drawn into the compressor when it restarts. This feature can be enabled or disabled from this menu. If Pump-down is enabled, this feature will only function when the compressor is in Auto mode. If Pump-down is enabled, then:

The Auto-cycle feature is “disabled” automatically. Normally, the Pump-down Stop set-point will be set lower than the Auto-cycle Stop set-point. Therefore, as the suction pressure is pulled down, the compressor is prevented from shutting down prematurely via the Auto-cycle Stop set-point by automatically disabling the Auto-cycle feature.

The compressor will be placed into “Stop” mode after the suction pressure is equal to, or goes below the Pump-down Stop pressure.

Enable = enables the Pump-down. Uncheck the box to disable the Pump-down setpoints.

Pump-down Stop Pressure = this setpoint defines the suction pressure value in which the compressor will cycle off. Normally, this set-point is set below the Suction Pressure Auto-cycle Stop Pressure Set-point.

32

Image 32
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Menu Button Touch Screen LCD DisplayMain Screen Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Percent Volume Fail Low Control Temperature FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailAuxiliary Safety#1 Input Fail Low Start Oil Pressure FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com