Emerson VISSION 20/20 Suction Pressure SP#1 Fail, Suction Pressure SP#2 Fail, Suction Temp Fail

Page 63

Safety Failure Message

Suction Pressure SP#1 Fail -

This message will appear when the suction pressure falls below the safety setting of the Low Suction Pres- sure Trip Setpoint No.1. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer or bad analog channel.

Suction Pressure SP#2 Fail -

This message will appear when the suction pressure falls below the safety setting of the Low Suction Pres- sure Trip Setpoint No.2. In addition, this message will appear when the suction pressure reading rises above 300 PSI, indicating an open transducer.

Discharge Pressure SP#1 Fail –

This message will appear when the discharge pressure exceeds the safety setting of the Hi Dsch Press Trip Setpoint No. 1 . In addition, this message will appear when the discharge pressure reading falls below 30” Hg, indicating a shorted transducer.

Discharge Pressure SP#2 Fail –

This message will appear when the discharge pressure exceeds the safety setting of the Hi Dsch Press Trip Setpoint No. 2 . In addition, this message will appear when the discharge pressure reading falls below 30” Hg, indicating a shorted transducer.

Suction Temp Fail –

This message will appear when the suction temperature falls below the safety setting of the Low Suction Temperature Trip setpoint. In addition, this message will appear when the suction temperature rises above 400 degrees, indicating an open RTD.

Discharge Temp Fail –

This message will appear when the discharge temperature rises above the safety setting of the High Dis- charge Temperature Trip setpoint. In addition, this message will appear when the discharge temperature falls below -30 degrees, indicating a shorted RTD.

Oil Separator Start Temp Fail –

This message will appear when the Oil Separator Temp is below the Low Oil Separator Start Temp Trip setpoint. In addition this message will appear after the Oil Separator Temp Safety Changeover timer times out and the Oil Separator temperature fails to rise above the Low Oil Separator Start Temp Reset after the compressor is started.

Oil Separator Run Temp Fail –

This message will appear when the Oil Separator Temp is below the Low Oil Separator Run Temp Reset setpoint after the Oil Separator Temp Safety Changeover timer times out.

Percent Capacity Fail –

This message will appear if the percent capacity reading exceeds 300% or goes below –15%.

Percent Volume Fail –

This message will appear if the percent volume reading exceeds 300% or goes below –15%.

Low Control Temperature Fail –

This message will appear when the Process Control Temperature falls below the safety setting of the Lo Control Temperature Trip Setpoint. In addition, this message will appear when the Process Control Tem- perature rises above 300 degrees F, indicating an open RTD.

63

Image 63
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Voltage Source Proper Wire SizingVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Touch Screen LCD Display Main ScreenMenu Button LOG on Button IndicatorsMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Problem Reason Solution Slide Valve Trouble Shooting GuideProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Suction Pressure SP#2 Fail Percent Volume FailLow Control Temperature Fail Suction Pressure SP#1 FailLow Oil Injection Temp Fail Auxiliary Safety#1 Input FailLow Start Oil Pressure Fail Low Oil Pressure FailVission 20/20 Troubleshooting Guide Digital & Analog Boards DipswitchesDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com