Emerson VISSION 20/20 service manual

Page 22

OIL MANIFOLD PRESSURE - Default signal is 4-20Ma. Oil manifold pressure transducer range and calibration is set in the calibration screen.

VRS OIL INJECTION PRESSURE – Default signal is 4-20Ma. VRS oil injection pressure transducer range and calibra- tion is set in the calibration screen.

%SLIDE VALVE POSITION – Reads the 0-5 volt signal back from the slide position motor actuator to indicate cur- rent slide valve position.

%VOLUME POSITION – Reads the 0-5 volt signal back from the slide volume motor actuator to indicate current volume position.

SUCTION TEMPERATURE – Default signal is RTD. Suction temperature calibration is set in the calibration screen.

DISCHARGE TEMPERATURE – Default signal is RTD. Discharge temperature calibration is set in the calibration screen.

OIL SEPARATOR TEMPERATURE – Default signal is RTD. Oil separator temperature calibration is set in the calibra- tion screen.

OIL MANIFOLD TEMPERATURE – Default signal is RTD. Oil manifold temperature calibration is set in the calibra- tion screen.

PROCESS TEMPERATURE – Default signal is RTD. Process temperature calibration is set in the calibration screen.

LEVEL PROBE (COOL COMPRESSION) – Default signal is 4-20mA. Measures separator level. Level probe calibration is set in the calibration screen.

CONDENSER PRESSURE – Default signal is 4-20Ma. Condenser pressure transducer range and calibration is set in the calibration screen.

REMOTE CAPHOLD – Default signal is 4-20Ma. Active in “Direct I/O” mode. Adjusts the capacity of the compres- sor from 0-100%, proportional to the 4-20mA signal.

ECONOMIZER PRESSURE – Default signal is 4-20Ma. Economizer pressure transducer range and calibration is set in the calibration screen.

CHILLER IN TEMPERATURE – Default signal is RTD. Chiller inlet temperature calibration is set in the calibration screen.

MOTOR WINDING TEMPERATURE #1 thru #3 - Default signal is RTD. One RTD is installed in each of the three mo- tor windings to monitor motor winding temperature.

AUXILIARY #1 thru #7 – Flexible analog inputs that can be configured to control, alarm or trip.

BEARING TEMP #1 thru #4 - Default signal is RTD. Monitors bearing temperatures in both the compressor and motor.

22

Image 22
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Main Screen Touch Screen LCD DisplayMenu Button Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Suction Pressure SP#1 Fail Percent Volume FailLow Control Temperature Fail Suction Pressure SP#2 FailLow Oil Pressure Fail Auxiliary Safety#1 Input FailLow Start Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com