Emerson VISSION 20/20 service manual

Page 36

Current Transformer Ratio : The value entered must agree with the Current Transformer Ratio label on the current transformer being used. The current transformer is mounted in the compressor motor conduit box. The ratio is stated in terms of “Primary amps : Secondary amps”. The secondary value is always “5” amps. The primary number for the current transformer is selected based on the size of the motor being used. The primary number is the value that is entered for this set-point. For example if the current transformer ratio label reads 250:5, enter 250.

Low Suction Pressure Load Limit : Active in Discharge Pressure Capacity Control mode only. These setpoints limit the compressor from loading at low suction pressure conditions. They over-ride the discharge pressure capacity control setpoints. When the suction pressure is at or below the STOP LOAD setpoint then the com- pressor will not be allowed to load any further. If the suction pressure continues to fall, and is at or below the UNLOAD setpoint, then the capacity of the compressor will decrease until the suction pressure rises to a point that is between the UNLOAD and the STOP LOAD setpoint.

36

Image 36
Contents Control Panel Page Important Note Page Touch Screen LCD Display Optional Analog Input Jumper Tables Standard Vilter Warranty Page Operational Flow Charts Page Proper Wire Sizing Voltage SourceVoltage Source Grounding Mixing Voltages Wiring Methods DON’T Touch Screen Description Type Liquid Injection #2 Output Not Defined Page Analog Inputs Page Compressor VFD 20 mA Condenser VFD Slide Valve Position Touch Screen LCD Display Main ScreenMenu Button Indicators LOG on ButtonMenu Screen Page Compressor Control Time Proportioning Control Auto-Cycle Setpoints Other Setpoints That Might be Required for Motor PID Control Pump-down Pull-down Misc. Control Page Page Alarms and Trips Screen Page Alarms and Trips Page Timers Page Timers Service Options Instrument Calibration Slide Calibration Remove Cover Press Down On Photochopper Command Shaft Rotation Capacity Volume INC DEC CCW Slide Valve Operation Slide Valve Trouble Shooting Guide Problem Reason SolutionProblem Replace the actuator. See above Trend Chart Event List Screen Input / Output States Configuration Screens Page Page Maintenance Screen Log In Screen Screen to Add Users User Level Percent Volume Fail Low Control Temperature FailSuction Pressure SP#1 Fail Suction Pressure SP#2 FailAuxiliary Safety#1 Input Fail Low Start Oil Pressure FailLow Oil Pressure Fail Low Oil Injection Temp FailVission 20/20 Troubleshooting Guide Dipswitches Digital & Analog BoardsDipswitch Position Digital Output #2 Digital Input Digital Input/Output #1 Digital Input/Output #2 POSITION-1 JP-16 JP-19 JP-22 JP-27 JP-28 JP-29 JP-30 JP-31 POSITION-2 Jumper Position Analog Output Optional Analog Input Jumper Tables Channel #6 Signal Page EmersonClimate.com